Weil-McLain Boiler Error Codes

Find your code in the list below. Each page explains what the code means, the most likely causes, step-by-step fixes you can do yourself, and the parts that commonly resolve it. 20 codes covered.

Finding your model number: it is on the rating plate on the boiler jacket, often behind the front panel.

Tap any code for its full fix — causes, step-by-step checks, and the parts that commonly fix it.

ECO Tec (plain-language fault displays)

Faults show as plain-language messages on the control display (IGNITION 1 FAULT, LOW WTR CUTOFF OPEN) rather than numbers; the manual's fault table states each one's reset behaviour - auto reset, timed retry, or manual reset.

CodeWhat it meansCheck first
Air Pressure Switch OpenThe air pressure switch connection is open, so the control cannot prove that combustion air is moving and…Blocked or restricted vent or intake piping›
Blower Fault 1The blower does not reach zero RPM within four minutes when the boiler is in Standby or Prepump mode. A…Loose or disconnected low voltage wires to the blower motor›
Blower Fault 2The blower is unable to reach the required pre-purge speed or the ignition speed, or it failed to complete…Loose or damaged wires on the high voltage blower motor harness›
Blower Fault 3The blower ran outside its minimum or maximum speed range for ten seconds. The control drives the blower to a…Loose or damaged wires on the high voltage or low voltage blower motor harnesses›
Closure Switch faultThe proof of closure connections on J18A pins 2 and 3 are open, so a device that must prove closed before…Factory jumper loose or on the wrong pins at J22 or the closure connection›
Configuration faultThe configuration data stored in the control safety micro does not match the data in the control application…Control settings changed or corrupted so the two stored copies disagree›
Control faultThe microcontrollers on the main control board have reported a RAM or ROM error, so the control no longer…RAM error in the main control board›
DHW Outlet > Boiler OutOn Combi models only, the DHW outlet sensor reads more than 10 degrees F above the boiler outlet sensor and…Insufficient water flow delivered by the installed circulators›
FALSE FLAMEThe control is detecting a flame signal when there should be no flame. Either flame is genuinely still…Gas valve not closing, so flame continues after shutdown›
FLAME LOSS FAULTThe boiler went through five ignition attempts and the flame value dropped below proof of ignition during the…Restricted or blocked flue pipe or intake pipe›
FLUE TEMP TOO HIGHThe flue temperature sensor has passed 210 degrees F, which is the warning level, or 220 degrees F, which is…Buildup or abnormal wear in the heat exchanger, combustion chamber or flue ways›
GAS RELAY FAULTThe control has detected a problem with the gas valve output circuit, shown as GAS RELAY FAULT 1 through 4…Loose or damaged wiring between the gas valve and the control›
HIGH TEMP LIMITThe boiler temperature sensor has reached the High Temp Limit setting, so the control has shut the burner…High limit setting less than 10 degrees F above the maximum target temperature plus the›
IGNITION 1 FAULTThe boiler went through five ignition attempts and never detected flame at all, or the flame sense value…Blocked condensate trap letting condensate build up in the heat exchanger›
IGNITION 2 FAULTThe boiler went through five ignition attempts and lit, but the flame never reached the running flame…Fouled or worn igniter or ignition electrode›
LIMIT OPENA manual reset or automatic reset external limit device wired to the control has opened, breaking the safety…External safety limit device opened on a real condition›
LOW WTR CUTOFF OPENThe internal low water cutoff contacts are open, so the control is treating the boiler as low on water and…Low water condition in the system›
RETURN > SUPPLYThe return water temperature is higher than the supply temperature by 10 degrees F or more, and the burner…Boiler circulator moving water in the wrong direction›
Supply 60F > ReturnOne of the boiler out temperatures is more than 60 degrees F above the boiler in temperature while the burner…Inadequate water flow through the boiler›
TEMP RISE TOO QUICKLYThe supply water temperature inside the heat exchanger rose faster than 10 degrees F per second during the…Piping installed incorrectly for the boiler›

Common questions

What does IGNITION 1 FAULT mean on a Weil-McLain ECO Tec?
The boiler made 5 ignition attempts and never proved flame - the flame sense never reached its minimum threshold. The manual's checks run from the condensate trap and ignition cable (1,000 ohms +/-50) to the igniter gap (4.5 mm) and gas pressure.

What does LOW WTR CUTOFF OPEN mean?
The low water cutoff has opened and the fault needs a manual reset: check the boiler's water level first, then the LWCO probe and its status in Diagnostics - Inputs, before suspecting the control.

Looking for a part?

Once you know the part you need, browse Weil-McLain Boiler replacement parts → The parts shelves are organized by brand, with the parts that actually fix these codes.