Weil-McLain Boiler ECO Tec 80/110/150/199 LOW WTR CUTOFF OPEN Error Code

What the LOW WTR CUTOFF OPEN code means

The internal low water cutoff contacts are open, so the control is treating the boiler as low on water and will not fire it. The control needs a manual reset if the contacts are open. The cause is either a real low water condition in the system or a dirty or failed cutoff probe.

Likely causes

  1. Low water condition in the system
  2. Dirty low water cutoff probe
  3. Loose wiring between the low water cutoff and the control
  4. Failed low water cutoff

How to fix it — step by step

  1. Record the display text before resetting anything, and note the system pressure gauge reading.
  2. Safety: do not fire the boiler to test it while a low water condition is possible. Switch the service switch off before removing any device.
  3. Locate the low water cutoff probe in the boiler and open Diagnostics, Inputs on the display to read its status. OPEN there confirms the control really sees open contacts.
  4. Test: if the system is confirmed full of water, check the wiring between the cutoff and the control for looseness. Tight wiring with the input still OPEN points at the probe itself.
  5. End at the fix: repair the low water condition if one exists. If the water level is correct, remove and clean the probe, and if the fault still exists, replace the low water cutoff. → Shop the low water cutoff (lwco) at Amazon

Did that fix it?

Worked through the steps? Say where you landed - it pinpoints what to do next.

Parts that commonly fix the LOW WTR CUTOFF OPEN code

What fixed yours?

Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.

Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.

Manual & model number

Find your model number on the rating plate on the boiler jacket, often behind the front panel. It's the key to the right manual pages and the right parts.

Related Weil-McLain Boiler ECO Tec 80/110/150/199 error codes

See all Weil-McLain ECO Tec 80/110/150/199 codes & guides →