Weil-McLain Boiler ECO Tec 80/110/150/199 Supply 60F > Return

What this problem usually means

One of the boiler out temperatures is more than 60 degrees F above the boiler in temperature while the burner has been on for less than two minutes, or the spread has grown past 60 degrees F in normal firing. A spread that wide means water is barely moving through the boiler. The control retries on a lengthening timer, from two and a half minutes up to six and a half minutes, and keeps retrying as long as the temperatures come back under 60 degrees F apart.

Likely causes

  1. Inadequate water flow through the boiler
  2. Circulators undersized for the system
  3. Circulators installed incorrectly or wired incorrectly
  4. On Combi applications, no pre-pump time to mix and circulate water before firing

How to fix it — step by step

  1. Record the display text and the boiler out and boiler in temperatures from Diagnostics.
  2. Safety: switch the service switch off before touching circulator wiring or piping valves.
  3. Locate the boiler circulator and confirm it is installed in the correct orientation and actually runs on a call for heat.
  4. Test: restore power and call for heat while watching the two temperatures. A spread that races past 60 degrees F while the return pipe stays cool confirms low flow. A spread that stays narrow with verified flow points back at a sensor reading problem.
  5. End at the fix: ensure proper flow through the boiler, size or re-speed the circulators correctly for the system, and correct any circulator wiring. On Combi applications, add a pre-pump time to the Combi priority to mix and circulate water before firing.

Did that fix it?

Worked through the steps? Say where you landed - it pinpoints what to do next.

Parts that commonly fix it

What fixed yours?

Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.

Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.

Manual & model number

Find your model number on the rating plate on the boiler jacket, often behind the front panel. It's the key to the right manual pages and the right parts.