Weil-McLain Boiler ECO Tec 80/110/150/199 Blower Fault 2

What this problem usually means

The blower is unable to reach the required pre-purge speed or the ignition speed, or it failed to complete its calibration within four minutes. Without proven airflow at the right speed the boiler cannot purge or light safely. The fault clears automatically after one hour.

Likely causes

  1. Loose or damaged wires on the high voltage blower motor harness
  2. Loose or damaged wires on the low voltage blower motor harness
  3. Blower calibration lost or never completed
  4. Failed blower motor

How to fix it — step by step

  1. Record the display text and note whether the blower runs at all during pre-purge.
  2. Safety: switch the service switch off and verify power is off before handling blower wiring.
  3. Locate the blower and check both its high voltage and low voltage motor harnesses for loose or damaged wires and full pin engagement.
  4. Test: reseat the harnesses, restore power and re-calibrate the blower motor in the Boiler Settings menu. A blower that completes calibration and reaches purge speed was a connection or calibration problem. One that still cannot reach speed on sound wiring has failed. → Shop the blower at Amazon
  5. End at the fix: repair any harness damage found. If calibration and wiring are correct and the fault returns, replace the blower.

Did that fix it?

Worked through the steps? Say where you landed - it pinpoints what to do next.

Parts that commonly fix it

What fixed yours?

Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.

Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.

Manual & model number

Find your model number on the rating plate on the boiler jacket, often behind the front panel. It's the key to the right manual pages and the right parts.

Related Weil-McLain Boiler ECO Tec 80/110/150/199 problems

See all Weil-McLain ECO Tec 80/110/150/199 codes & guides →