Weil-McLain Boiler ECO Tec 80/110/150/199 RETURN > SUPPLY Error Code

What the RETURN > SUPPLY code means

The return water temperature is higher than the supply temperature by 10 degrees F or more, and the burner has been lit for more than 60 seconds. Water should always leave the boiler hotter than it returns, so this reading means flow is going the wrong way, a sensor is in the wrong place, or a sensor is wired to the wrong terminals. The fault resets automatically when the condition no longer exists.

Likely causes

  1. Boiler circulator moving water in the wrong direction
  2. System sensors placed on boiler loop piping instead of system piping
  3. Sensors wired to the wrong terminal locations
  4. Sensors placed too close to the boiler loop connection and heated inaccurately

How to fix it — step by step

  1. Record the display text and the supply and return temperatures shown in Diagnostics.
  2. Safety: switch the service switch off before moving sensors or changing wiring.
  3. Locate the boiler circulator and check its flow direction against the piping. Then locate the system sensors and confirm they sit on the system piping, not on the boiler loop.
  4. Test: compare the sensor readings with the actual pipe temperatures. Readings that follow the wrong pipe, or swap when the circulator direction is corrected, confirm a placement or wiring error rather than a failed sensor.
  5. End at the fix: correct the circulator direction, move the system sensors onto the system piping further from the boiler loop connection if needed, and correct any swapped sensor wiring. The fault clears on its own once return reads below supply.

Did that fix it?

Worked through the steps? Say where you landed - it pinpoints what to do next.

Parts that commonly fix the RETURN > SUPPLY code

Parts run $25–$80

Typical ranges, checked Nov 2026. Your model’s exact part can land outside them.

What fixed yours?

Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.

Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.