Weil-McLain Boiler ECO Tec 80/110/150/199 Blower Fault 3

What this problem usually means

The blower ran outside its minimum or maximum speed range for ten seconds. The control drives the blower to a commanded speed for each firing rate, and a blower that drifts out of range cannot hold the correct air delivery for combustion. The fault clears with a one hour automatic reset.

Likely causes

  1. Loose or damaged wires on the high voltage or low voltage blower motor harnesses
  2. Blower calibration out of adjustment
  3. Failed blower motor

How to fix it — step by step

  1. Record the display text and the firing rate the boiler was running at when it faulted.
  2. Safety: switch the service switch off and verify power is off before handling blower wiring.
  3. Locate the blower and inspect both motor harnesses for loose connections, damaged wires and pin engagement at the blower and at the chassis mount connection.
  4. Test: reseat the harnesses and re-calibrate the blower motor in the Boiler Settings menu, then run the boiler through its firing range. Speed that holds in range after calibration confirms the calibration was the problem. Speed that still drifts out condemns the blower.
  5. End at the fix: repair harness faults if found. If the blower still runs out of range after calibration on sound wiring, replace the blower. → Shop the blower at Amazon

Did that fix it?

Worked through the steps? Say where you landed - it pinpoints what to do next.

Parts that commonly fix it

What fixed yours?

Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.

Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.

Manual & model number

Find your model number on the rating plate on the boiler jacket, often behind the front panel. It's the key to the right manual pages and the right parts.