Weil-McLain Boiler ECO Tec 80/110/150/199 IGNITION 1 FAULT Error Code

What the IGNITION 1 FAULT code means

The boiler went through five ignition attempts and never detected flame at all, or the flame sense value never reached the minimum threshold for the boiler model. No flame after repeated tries usually comes down to the igniter, its cable, gas supply pressure, or a dirty burner and heat exchanger raising back pressure. The fault resets automatically after one hour, or sooner with a manual reset.

Likely causes

  1. Blocked condensate trap letting condensate build up in the heat exchanger
  2. Loose ignition cable connection
  3. Fouled, worn, bent or faulty igniter
  4. Dirty burner or heat exchanger causing high back pressure and poor ignition
  5. Incoming gas pressure outside the limits on the rating label
  6. Wrong boiler model or altitude selected in the control

How to fix it — step by step

  1. Record the display text and check whether any flame appeared at all during the attempts, if that was observed.
  2. Safety: switch the service switch off and close the gas shutoff before removing the igniter or opening the burner compartment.
  3. Locate the igniter and ignition cable at the burner. Access is through the burner compartment after the front panel is removed.
  4. Test: check the ignition cable resistance, which should measure 1000 ohms plus or minus 50 ohms, and check the igniter rods are parallel with a 4.5 mm spark gap. A cable outside that range or a damaged rod set explains a no-spark or weak-spark failure.
  5. End at the fix: clean a fouled ignition electrode with steel wool for further use, or replace a worn or badly fouled igniter. Clear any condensate trap blockage, clean the burner and heat exchanger if they are dirty, and correct gas pressure or model selection if those tested wrong.

Did that fix it?

Worked through the steps? Say where you landed - it pinpoints what to do next.

Parts that commonly fix the IGNITION 1 FAULT code

Parts run $15–$85

Typical ranges, checked Nov 2026. Your model’s exact part can land outside them.

What fixed yours?

Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.

Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.

Manual & model number

Find your model number on the rating plate on the boiler jacket, often behind the front panel. It's the key to the right manual pages and the right parts.

Related Weil-McLain Boiler ECO Tec 80/110/150/199 error codes