Weil-McLain Boiler ECO Tec 80/110/150/199 DHW Outlet > Boiler Out

What this problem usually means

On Combi models only, the DHW outlet sensor reads more than 10 degrees F above the boiler outlet sensor and the burner has been firing for at least 30 seconds. Domestic hot water should not be leaving hotter than the boiler water making it, so this points at poor water movement through the Combi circuit or a three-way valve problem. The fault clears when the DHW outlet sensor drops to less than the boiler outlet sensor plus 7 degrees F.

Likely causes

  1. Insufficient water flow delivered by the installed circulators
  2. Closed or partly closed valves in the DHW circuit
  3. Three-way valve not operating correctly

How to fix it — step by step

  1. Record the display text and both sensor temperatures from Diagnostics.
  2. Safety: switch the service switch off before working on valves or circulators, and be aware the DHW circuit can hold hot water.
  3. Locate the three-way valve in the Combi water circuit and the circulators serving the DHW priority.
  4. Test: check that the appropriate valves are open and confirm the installed circulators are delivering flow on the DHW priority. A three-way valve that does not change over when the priority switches is the failed part if flow and valves are otherwise correct.
  5. End at the fix: open any closed valves, correct the circulator setup, and repair or replace the three-way valve if it is not operating. The fault clears on its own once the temperature relationship returns to normal. → Shop the three-way valve at Amazon

Did that fix it?

Worked through the steps? Say where you landed - it pinpoints what to do next.

Parts that commonly fix it

What fixed yours?

Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.

Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.

Manual & model number

Find your model number on the rating plate on the boiler jacket, often behind the front panel. It's the key to the right manual pages and the right parts.

Related Weil-McLain Boiler ECO Tec 80/110/150/199 problems

See all Weil-McLain ECO Tec 80/110/150/199 codes & guides →