Coleman 268897-UUM-B control (Johnson Controls) Common Problems

Find your problem in the list below. Each page explains the most likely causes, step-by-step checks you can do yourself, when to call a pro, and the parts that commonly resolve it. 16 problems covered.

Tap any code for its full fix — causes, step-by-step checks, and the parts that commonly fix it.

ProblemWhat it meansCheck first
1 red flashFlame was sensed when there was no call for heat. The control turns on both the inducer motor and the supply…Gas valve leaking through›
10 red flashesGas flow with no call for heat. The control is reporting gas moving when the valve should be shut.Gas valve passing gas with no call›
11 red flashesA primary or auxiliary limit switch has stayed open for more than five minutes. With no airflow, the heat has…Failed blower motor›
12 red flashesOpen igniter circuit. The control cannot pass current through the igniter.Disconnected or loose igniter wire›
2 red flashesThe normally open pressure switch contacts are stuck in the closed position.Faulty pressure switch with contacts stuck closed›
3 red flashesThe pressure switch contact did not close after the inducer was energized, so the ignition sequence stops.Faulty inducer motor›
4 amber flashesThe control board is receiving a Y signal from the thermostat without a G signal. That means the thermostat…Thermostat wired so Y is connected without G›
4 red flashesA primary or auxiliary limit switch has opened. The furnace overheated, and the control runs the supply air…Dirty filter restricting airflow›
5 red flashesThe rollout switch has opened. The rollout control is manually reset, and this fault means flame or heat…Poor combustion air supply›
6 red flashesAfter the unit was operating, the pressure switch opened 4 times during the call for heat. The furnace locks…Vent or intake partially blocked so draft fades mid cycle›
7 red flashesFlame could not be established. The no light condition occurred 3 times during the call for heat, and the…Low gas pressure›
8 red flashesFlame was lost 5 times during the heating cycle. The furnace locks out for one hour and then restarts.Low gas pressure›
9 red flashesReversed line voltage polarity, or a grounding problem. Both heating and cooling operation are affected.Line voltage polarity reversed at the furnace or the branch circuit›
Rapid amber flashFlame sense current is below 1.5 microamps. The furnace runs, but the flame signal is weak.Dirty or oxidized flame sensor›
Rapid red flashTwinning error, or incorrect 24 volt phasing. The control is reporting a wiring or phasing problem, most…Twinning wiring error on a twinned pair of furnaces›
Steady on redControl failure. The failure is internal to the control, and the control should be replaced.Internal failure inside the furnace control›