Coleman Furnace 268897-UUM-B control (Johnson Controls) 4 amber flashes

What this problem usually means

The control board is receiving a Y signal from the thermostat without a G signal. That means the thermostat wiring is wrong, since a cooling call should also call the fan.

Likely causes

  1. Thermostat wired so Y is connected without G
  2. Thermostat failed internally bridging the cooling call
  3. Wrong thermostat type for the furnace

How to fix it — step by step

  1. Turn the power off before working on thermostat wiring.
  2. At the control board, find the thermostat wires on the R, G, and Y terminals. The fault means a Y signal arrives with no G signal.
  3. Check for a stray wire strand bridging terminals, or a Y wire landed on the wrong terminal. Correct the wiring to match the diagram inside the blower door.
  4. Check the same connections at the thermostat base.
  5. Restore power and call for cooling with the fan set to auto. A correct call brings Y and G together and clears the code. A code that returns with proven wiring means the thermostat itself is faulty. → Shop the thermostat at Amazon

Did that fix it?

Worked through the steps? Say where you landed - it pinpoints what to do next.

Parts that commonly fix it

Parts run $70–$280Typical pro repair $133–$505

Typical ranges, checked Nov 2026. Your model’s exact part can land outside them.

What fixed yours?

Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.

Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.

Manual & model number

Find your model number inside the blower/burner compartment door. It's the key to the right manual pages and the right parts.

Related Coleman Furnace 268897-UUM-B control (Johnson Controls) problems

See all Coleman 268897-UUM-B control (Johnson Controls) codes & guides →