Coleman Furnace 268897-UUM-B control (Johnson Controls) 2 red flashes
What this problem usually means
The normally open pressure switch contacts are stuck in the closed position.
Likely causes
- Faulty pressure switch with contacts stuck closed
- Miswired pressure switch circuit
How to fix it — step by step
- The control confirms the pressure switch contacts are open at the start of each heat cycle. On this code they are not.
- Turn the power off, then find the pressure switch near the inducer, a round switch with a rubber hose and two wires.
- Check the wiring against the diagram for a miswired connection, especially after any recent part replacement.
- Pull the hose and test the switch with a meter with the inducer off. Continuity with no draft means the switch is stuck.
- Replace a stuck pressure switch with the correct setpoint part.
- Verify the fix: restore power and run a full heat call from the thermostat and watch one complete heating cycle - ignition, steady burn and shutoff - the furnace should complete the cycle with no code returning. If it comes back, the fault is still present: recheck the step above whose result was borderline, and treat the part that step points to as the one to replace
Did that fix it?
Worked through the steps? Say where you landed - it pinpoints what to do next.
Good - you're done. If it comes back, the causes at the top of this page are where to look first.
Then the likely broken part is the pressure switch.
Parts that commonly fix it
- pressure switch$50–$205Shop at Amazon
- Tools for this job, if you need them$15–$65
Typical ranges, checked Nov 2026. Your model’s exact part can land outside them.
What fixed yours?
Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.
Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.
Manual & model number
Find your model number inside the blower/burner compartment door. It's the key to the right manual pages and the right parts.
Related Coleman Furnace 268897-UUM-B control (Johnson Controls) problems
- 3 red flashes
- 4 amber flashes
- 4 red flashes
- 5 red flashes
- 6 red flashes
- 7 red flashes
- 8 red flashes
- 9 red flashes
- Rapid amber flash
- Rapid red flash
- Steady on red
- 1 red flash
See all Coleman 268897-UUM-B control (Johnson Controls) codes & guides →