Coleman Furnace 268897-UUM-B control (Johnson Controls) 3 red flashes
What this problem usually means
The pressure switch contact did not close after the inducer was energized, so the ignition sequence stops.
Likely causes
- Faulty inducer motor
- Blocked vent pipe
- Broken or disconnected pressure switch hose
- Faulty pressure switch
How to fix it — step by step
- Turn the power off before opening any panel.
- Find the pressure switch by the inducer and check its hose. Reconnect or replace a broken hose.
- Check the vent pipe end to end and the outdoor termination for blockage.
- Restore power and call for heat. The inducer should start first. An inducer that does not run, or runs weak and noisy, is the fault.
- If the inducer runs strong with a clear vent and good hose, test the switch during the run. No closure means the switch has failed.
- Replace the pressure switch with the correct setpoint part. Inducer replacement is pro work for most owners.
- Verify after the repair: restore power and run a full heat call from the thermostat and watch one complete heating cycle - ignition, steady burn and shutoff - the furnace should complete the cycle with no code returning. If it comes back, the repair did not cure it: hand over the point in the sequence where it reappears, because that timing is the diagnosis
Did that fix it?
Worked through the steps? Say where you landed - it pinpoints what to do next.
Good - you're done. If it comes back, the causes at the top of this page are where to look first.
This fault usually needs a technician - but this is the part they would test first.
Then the likely broken part is the pressure switch.
Shop the pressure switch at Amazon
Also tied to this fault: inducer motor - Shop at Amazon
Parts that commonly fix it
- pressure switch$50–$205Shop at Amazon
- inducer motor$50–$215Shop at Amazon
Typical ranges, checked Nov 2026. Your model’s exact part can land outside them.
What fixed yours?
Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.
Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.
Manual & model number
Find your model number inside the blower/burner compartment door. It's the key to the right manual pages and the right parts.
Related Coleman Furnace 268897-UUM-B control (Johnson Controls) problems
- 4 amber flashes
- 4 red flashes
- 5 red flashes
- 6 red flashes
- 7 red flashes
- 8 red flashes
- 9 red flashes
- Rapid amber flash
- Rapid red flash
- Steady on red
- 1 red flash
- 10 red flashes
See all Coleman 268897-UUM-B control (Johnson Controls) codes & guides →