Coleman Furnace 268897-UUM-B control (Johnson Controls) Rapid amber flash
What this problem usually means
Flame sense current is below 1.5 microamps. The furnace runs, but the flame signal is weak.
Likely causes
- Dirty or oxidized flame sensor
- Low gas flow giving a weak flame
- Sensor positioned at the edge of the flame
How to fix it — step by step
- The manual puts the low flame warning at below 1.5 microamps, with normal sense current about 3.7 microamps on this control.
- Turn the power off, find the flame sensor rod in the burner flame path, and clean it with fine steel wool until bright.
- Reinstall the sensor fully in the flame and restore power.
- Measure the flame current at the flame current test pad on the control if you have a meter. A reading back above 1.5 microamps confirms the cleaning fixed it.
- If the reading stays low with a clean sensor, call a pro to check gas flow and manifold pressure.
- Verify after the repair: restore power and run a full heat call from the thermostat and watch one complete heating cycle - ignition, steady burn and shutoff - the furnace should complete the cycle with no code returning. If it comes back, the repair did not cure it: hand over the point in the sequence where it reappears, because that timing is the diagnosis
Did that fix it?
Worked through the steps? Say where you landed - it pinpoints what to do next.
Good - you're done. If it comes back, the causes at the top of this page are where to look first.
This fault usually needs a technician - but this is the part they would test first.
Then the likely broken part is the flame sensor.
Parts that commonly fix it
- flame sensor$10–$60Shop at Amazon
Typical ranges, checked Nov 2026. Your model’s exact part can land outside them.
What fixed yours?
Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.
Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.
Manual & model number
Find your model number inside the blower/burner compartment door. It's the key to the right manual pages and the right parts.
Related Coleman Furnace 268897-UUM-B control (Johnson Controls) problems
- Rapid red flash
- Steady on red
- 1 red flash
- 10 red flashes
- 11 red flashes
- 12 red flashes
- 2 red flashes
- 3 red flashes
- 4 amber flashes
- 4 red flashes
- 5 red flashes
- 6 red flashes
See all Coleman 268897-UUM-B control (Johnson Controls) codes & guides →