Amana Heat pump AVZC20 series E22 Error Code
What the E22 code means
Shown as PCB LED display 22 on the outdoor unit and transmitted to the ComfortNet thermostat as ClimateTalk fault E22, this is the AVZC20 outdoor chart's 'HI DISCH TEMP' - high discharge temperature. The thermostat message says the equipment is experiencing frequent high discharge temperature faults. Probable causes listed are a discharge thermistor inoperable or improperly connected, a discharge thermistor in the incorrect position or off, low refrigerant charge, overcharge, or a faulty compressor, with corrective actions to check the discharge thermistor's resistance, connections and position, check refrigerant charge level, and check the compressor. Sustained high discharge temperature cooks compressor oil, so repeated E22s are not a code to keep resetting.
Likely causes
- Low refrigerant charge
- Refrigerant overcharge
- Discharge thermistor inoperable, improperly connected, or off its correct position
- Faulty compressor
How to fix it — step by step
- Record the code before cycling power: note the number on the outdoor unit's PCB LED display and the transmitted ClimateTalk fault code (for example E22) shown at the ComfortNet thermostat, and write down whether the unit was heating, cooling or in defrost when it appeared.
- Safety: switch the thermostat off, open the outdoor disconnect and the breaker, verify 0 VAC at the outdoor control with a meter before touching wiring, and treat capacitors and the inverter board as charged - wait and re-verify 0 V before handling them.
- Locate the part: the discharge thermistor is clipped on the compressor discharge line near the compressor in the base of the AVZC20 outdoor unit, wired to the outdoor control board in the control compartment, where the code is read on the board's LED display.
- Test: with power off, confirm the discharge thermistor is actually seated on the discharge line in its correct position and measure its resistance - an open/shorted thermistor or one hanging off the line proves a sensing fault rather than a hot compressor. True discharge temperature and charge verification are gauge/temperature work on the sealed system. → Shop the thermistor at Amazon
- End at the pinpoint: reposition or replace the discharge Thermistor as its test condemns; if the sensor is proven good, the pinpoint is a genuine high discharge temperature from charge or compressor faults, which is EPA-certified technician work only.
Did that fix it?
Worked through the steps? Say where you landed - it pinpoints what to do next.
Good - you're done. If it comes back, the causes at the top of this page are where to look first.
This fault usually needs a technician - but this is the part they would test first.
Then the likely broken part is the Thermistor.
Parts that commonly fix the E22 code
- Thermistor$25–$80Shop at Amazon
Typical ranges, checked Nov 2026. Your model’s exact part can land outside them.
What fixed yours?
Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.
Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.
Manual & model number
Working on a specific model? The official Amana manual is on Amana's support site — you'll need your model number.
Find your model number on the outdoor unit's rating plate. It's the key to the right manual pages and the right parts.