Amana Heat pump AVZC20 series E30 Error Code

What the E30 code means

Shown as PCB LED display 30 on the outdoor unit and transmitted to the ComfortNet thermostat as ClimateTalk fault E30, this is the AVZC20 outdoor chart's 'OD CTRL FAIL3,' the third outdoor-control failure code in the AVZC20 chart (after E12 and E18). The thermostat message is the same board-level verdict: it indicates the control board may need to be replaced, and the chart's probable causes are wiring to the control board disconnected or a faulty control board, with corrective actions to check the wiring to the control board and replace the control board if necessary. As with the other OD CTRL FAIL codes, external causes are limited to the board's own wiring.

Likely causes

  1. Wiring to the outdoor control board disconnected
  2. Faulty outdoor control board

How to fix it — step by step

  1. Record the code before cycling power: note the number on the outdoor unit's PCB LED display and the transmitted ClimateTalk fault code (for example E30) shown at the ComfortNet thermostat, and write down whether the unit was heating, cooling or in defrost when it appeared.
  2. Safety: switch the thermostat off, open the outdoor disconnect and the breaker, verify 0 VAC at the outdoor control with a meter before touching wiring, and treat capacitors and the inverter board as charged - wait and re-verify 0 V before handling them.
  3. Locate the part: the outdoor control board is in the AVZC20 outdoor unit's control compartment behind its access panel, with its power and signal harnesses plugged into it; E30 is read on that board's LED display and at the ComfortNet thermostat.
  4. Test: with power off, reseat and inspect every harness plugged into the outdoor control board and check for a disconnected or damaged lead - the chart names disconnected wiring as the external cause. A board with all wiring proven connected and correct supply voltage that still sets E30 has failed internally. → Shop the control board at Amazon
  5. End at the fix: repair/reconnect the board wiring if that was the fault; otherwise replace the outdoor Control board, restore power, run the system setup/test and confirm E30 does not return. Inverter board work is technician work.

Did that fix it?

Worked through the steps? Say where you landed - it pinpoints what to do next.

Parts that commonly fix the E30 code

What fixed yours?

Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.

Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.

Manual & model number

Working on a specific model? The official Amana manual is on Amana's support site — you'll need your model number.

Find your model number on the outdoor unit's rating plate. It's the key to the right manual pages and the right parts.