Amana Heat pump AVZC20 series E32 Error Code
What the E32 code means
Shown as PCB LED display 32 on the outdoor unit and transmitted to the ComfortNet thermostat as ClimateTalk fault E32, this is the AVZC20 outdoor chart's 'HI TEMP CTRL1' - a critical high-temperature fault on the outdoor control board itself. The thermostat message says the equipment is experiencing high temperature faults on the outdoor control board. The chart's probable causes centre on the board's cooling: ambient air conditions too high, cooling bracket screws missing or not properly fastened, no or poor thermal grease between the cooling plumbing and the cooling bracket on the control board, outdoor fan low speed (5-ton), or no/limited flow through the board's cooling circuit (restriction or low refrigerant) and a stop valve not completely open on 2-4 ton models.
Likely causes
- Ambient air conditions too high
- Cooling bracket screws missing or loose on the control board
- No/poor thermal grease between cooling plumbing and board cooling bracket
- Outdoor fan low speed (5-ton models)
- Restricted or low refrigerant flow through the board cooling circuit
How to fix it — step by step
- Record the code before cycling power: note the number on the outdoor unit's PCB LED display and the transmitted ClimateTalk fault code (for example E32) shown at the ComfortNet thermostat, and write down whether the unit was heating, cooling or in defrost when it appeared.
- Safety: switch the thermostat off, open the outdoor disconnect and the breaker, verify 0 VAC at the outdoor control with a meter before touching wiring, and treat capacitors and the inverter board as charged - wait and re-verify 0 V before handling them.
- Locate the part: the outdoor control board and its cooling bracket/plumbing are in the AVZC20 outdoor unit's control compartment (access panel off) - on 2-4 ton models the board is cooled by a refrigerant cooling circuit with a bracket and thermal grease; the code is read on the board's LED display.
- Test: with power off, verify the cooling bracket screws are present and secure and inspect the thermal grease contact between the cooling plumbing and bracket - missing screws or dry/absent grease exactly match the chart's causes. Check the outdoor fan runs at proper speed (5-ton) and that stop valves are fully open; refrigerant flow through the cooling circuit is proven with gauges, which is certified work.
- End at the pinpoint: secure the bracket screws and renew the thermal grease as found, or repair the Outdoor fan motor circuit; if the board's cooling hardware is proven correct, the pinpoint is restricted/low refrigerant flow in the cooling circuit, which is EPA-certified work. Repeated E32 risks inverter board failure.
Did that fix it?
Worked through the steps? Say where you landed - it pinpoints what to do next.
Good - you're done. If it comes back, the causes at the top of this page are where to look first.
This fault usually needs a technician - but this is the part they would test first.
Then the likely broken part is the Outdoor fan motor.
Shop the Outdoor fan motor at Amazon
Also tied to this fault: Control board - Shop at Amazon
Parts that commonly fix the E32 code
- Outdoor fan motorShop at Amazon
- Control boardShop at Amazon
What fixed yours?
Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.
Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.