Lochinvar Boiler Knight 81-286 (SMART SYSTEM) Outlet Sensor Fault

What this problem usually means

Outlet Sensor Fault is a manual reset lockout raised when the control reads the outlet sensor as open or shorted. Wiring is checked first, then the sensor resistance is compared with Table 3-2C, and the control module is the last suspect. The outlet sensor is a primary control input, so the boiler will not run without a valid reading.

Likely causes

  1. Control reads the outlet sensor as open or shorted
  2. Outlet sensor wiring disconnected or damaged
  3. Faulty outlet sensor
  4. Faulty control module

How to fix it — step by step

  1. Record the fault before resetting: write down 'Outlet Sensor Fault' exactly as shown on the SMART SYSTEM display, and note that most Knight lockouts need a manual reset with the RESET button on the SMART SYSTEM display after the condition is corrected.
  2. Safety: shut the boiler down, isolate power and close the gas shut-off valve before opening the cabinet or testing wiring. Gas pressure, gas valve and combustion checks are qualified technician work.
  3. Locate the parts: the outlet water temperature sensor is fitted in the boiler outlet waterway and wired to the control module, and the fault is read on the SMART SYSTEM display.
  4. Test: check the wiring to the sensor, make sure it is connected and not damaged, and reconnect or repair it as needed. Measure the sensor resistance and compare it with Table 3-2C on page 35 of the service manual; out of table means the sensor has failed.
  5. End at the fix: replace the outlet sensor if it tests out of range, then press RESET on the SMART SYSTEM display. A good sensor on good wiring pinpoints the control module. → Shop the control module at Amazon

Did that fix it?

Worked through the steps? Say where you landed - it pinpoints what to do next.

Parts that commonly fix it

Parts run $25–$80

Typical ranges, checked Nov 2026. Your model’s exact part can land outside them.

What fixed yours?

Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.

Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.

Manual & model number

Find your model number on the rating plate on the boiler jacket, often behind the front panel. It's the key to the right manual pages and the right parts.