Lochinvar Boiler Knight 81-286 (SMART SYSTEM) Blocked Drain SW
What this problem usually means
Blocked Drain SW is a manual reset lockout raised when the blocked drain switch detects excessive condensate build up inside the unit. Condensate that cannot drain away backs up until the switch stops the boiler. The drain path from the unit to the floor drain is the first place to look.
Likely causes
- Excessive condensate build up inside the unit
- Condensate tube obstructed or badly installed
- Condensate trap blocked
- Loose wiring at the wire harness plug
- Bad blocked drain switch
How to fix it — step by step
- Record the fault before resetting: write down 'Blocked Drain SW' exactly as shown on the SMART SYSTEM display, and note that most Knight lockouts need a manual reset with the RESET button on the SMART SYSTEM display after the condition is corrected.
- Safety: shut the boiler down, isolate power and close the gas shut-off valve before opening the cabinet or testing wiring. Gas pressure, gas valve and combustion checks are qualified technician work.
- Locate the parts: the condensate trap is at the bottom of the boiler, the condensate tube runs from the unit to the floor drain, the blocked drain switch sits in that drain path, and the fault is read on the SMART SYSTEM display.
- Test: check the condensate tube for proper installation and obstructions, inspect the condensate trap for blockage and clean it if necessary, and check the wiring connection at the wire harness plug. A clear, free draining path with the fault returning condemns the blocked drain switch itself.
- End at the fix: clear the trap or tube, correct the drain run, then press RESET on the SMART SYSTEM display. If the drain is proven clear, the pinpoint is the blocked drain switch and it is replaced.
Did that fix it?
Worked through the steps? Say where you landed - it pinpoints what to do next.
Good - you're done. If it comes back, the causes at the top of this page are where to look first.
This fault usually needs a technician - but this is the part they would test first.
Then the likely broken part is the Blocked drain switch.
Shop the Blocked drain switch at Amazon
Also tied to this fault: Condensate trap - Shop at Amazon
Parts that commonly fix it
- Blocked drain switchShop at Amazon
- Condensate trapShop at Amazon
What fixed yours?
Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.
Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.
Manual & model number
Find your model number on the rating plate on the boiler jacket, often behind the front panel. It's the key to the right manual pages and the right parts.
Related Lochinvar Boiler Knight 81-286 (SMART SYSTEM) problems
- Delta T High
- Fan Speed Low / High
- Fatal Error
- Flame Fail Ign
- Flame Sequence
- Flow Switch/LWCO
- Flue Sensor Fault
- Flue Temp Diff
- Flue Temp High
- Flue Temp Limit
- Gas Pressure SW
- GV/Relay Fail
See all Lochinvar Knight 81-286 (SMART SYSTEM) codes & guides →