Lochinvar Boiler Knight 81-286 (SMART SYSTEM) APS / HEX Temp Sw Open

What this problem usually means

APS / HEX Temp Sw Open is a manual reset lockout raised when either the air pressure switch contacts are open or the O-temp heat exchanger switch has opened. The air pressure side covers intake length, blockages and the switch's reference hoses, while the O-temp switch side, on the 286 model, covers refractory breakdown at the back of the inner combustion chamber. The two halves are tested separately.

Likely causes

  1. Air pressure switch contacts open
  2. Air intake length over the maximum allowed
  3. Obstruction in the air intake pipes or terminations
  4. Blocked reference hoses to the air pressure switch
  5. O-temp heat exchanger switch open, refractory breakdown (286 model)

How to fix it — step by step

  1. Record the fault before resetting: write down 'APS / HEX Temp Sw Open' exactly as shown on the SMART SYSTEM display, and note that most Knight lockouts need a manual reset with the RESET button on the SMART SYSTEM display after the condition is corrected.
  2. Safety: shut the boiler down, isolate power and close the gas shut-off valve before opening the cabinet or testing wiring. Gas pressure, gas valve and combustion checks are qualified technician work.
  3. Locate the parts: the air pressure switch is inside the cabinet with reference hoses to the air path, the O-temp switch is on the heat exchanger at the back of the inner combustion chamber, and the fault is read on the SMART SYSTEM display.
  4. Test: for the APS, check the switch wiring is on the common and normally closed terminals, confirm intake lengths are within the allowed maximum, clear any intake obstruction, and check the reference hoses for blockage, then inspect the burner and heat exchanger. For the O-temp switch, inspect the refractory at burner level and check continuity across both contacts of the normally closed switch.
  5. End at the fix: correct the intake, hose, burner or heat exchanger fault found, or replace the faulty air pressure switch or O-temp switch the tests condemn, then press RESET on the SMART SYSTEM display. Broken refractory with the unit fired means heat exchanger replacement, which is major technician work.

Did that fix it?

Worked through the steps? Say where you landed - it pinpoints what to do next.

Parts that commonly fix it

Parts run $50–$205

Typical ranges, checked Nov 2026. Your model’s exact part can land outside them.

What fixed yours?

Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.

Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.

Manual & model number

Find your model number on the rating plate on the boiler jacket, often behind the front panel. It's the key to the right manual pages and the right parts.