Lochinvar Boiler Knight 81-286 (SMART SYSTEM) Outlet Temp Diff
What this problem usually means
Outlet Temp Diff is a manual reset lockout raised when the control module reads an excessive temperature difference between the two sensors. A real difference that large points at a sensor reading wrong rather than water truly behaving that way, so both sensors and their wiring are proved before defaults or the module are touched. Restoring control parameter defaults from the optional PC software is one of the listed steps.
Likely causes
- Excessive temperature difference between the two sensors
- Faulty sensor or sensor wiring
- Control parameter fault
- Faulty control module
How to fix it — step by step
- Record the fault before resetting: write down 'Outlet Temp Diff' exactly as shown on the SMART SYSTEM display, and note that most Knight lockouts need a manual reset with the RESET button on the SMART SYSTEM display after the condition is corrected.
- Safety: shut the boiler down, isolate power and close the gas shut-off valve before opening the cabinet or testing wiring. Gas pressure, gas valve and combustion checks are qualified technician work.
- Locate the parts: the two sensors are the inlet and outlet water temperature sensors in the boiler waterways, both wired to the control module, and the fault is read on the SMART SYSTEM display.
- Test: check the wiring to each sensor for connection and damage, then measure each sensor's resistance and compare it with Table 3-2C on page 35 of the service manual. One sensor reading far from the other at the same water temperature is the pinpoint; two agreeing sensors move the fault to parameters or the module.
- End at the fix: replace the sensor the resistance test condemns, or restore the control parameter defaults from the optional PC software, then press RESET on the SMART SYSTEM display. Both exhausted pinpoints the control module. → Shop the control module at Amazon
Did that fix it?
Worked through the steps? Say where you landed - it pinpoints what to do next.
Good - you're done. If it comes back, the causes at the top of this page are where to look first.
This fault usually needs a technician - but this is the part they would test first.
Then the likely broken part is the Outlet water temperature sensor.
Shop the Outlet water temperature sensor at Amazon
Also tied to this fault: Inlet water temperature sensor - Shop at Amazon; Control module - Shop at Amazon
Parts that commonly fix it
- Outlet water temperature sensor$25–$80Shop at Amazon
- Inlet water temperature sensor$25–$80Shop at Amazon
- Control moduleShop at Amazon
- Tools for this job, if you need them$15–$65
Typical ranges, checked Nov 2026. Your model’s exact part can land outside them.
What fixed yours?
Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.
Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.
Manual & model number
Find your model number on the rating plate on the boiler jacket, often behind the front panel. It's the key to the right manual pages and the right parts.
Related Lochinvar Boiler Knight 81-286 (SMART SYSTEM) problems
- Outlet Temp High
- Parameters Progr
- Rem Ctrl Flt
- Sensor Open
- Sensor Shorted
- Service Blk
- Anti-cycling
- APS / HEX Temp Sw Open
- Blocked Drain SW
- Delta T High
- Fan Speed Low / High
- Fatal Error
See all Lochinvar Knight 81-286 (SMART SYSTEM) codes & guides →