Lochinvar Boiler Knight 81-286 (SMART SYSTEM) Fan Speed Low / High
What this problem usually means
Fan Speed Low / High, also shown as Fan Low/High, is a manual reset lockout raised when the actual fan RPM is about 30 percent away from what is being called for, low or high. Long or blocked vent and air intake runs are the first suspects, followed by the fan wiring, the fan itself and the main control board. A blown fuse is also listed against the fan fault group.
Likely causes
- Actual fan RPM 30 percent lower or higher than called for
- Vent or air intake lengths over the maximum allowed
- Obstruction in the vent or air intake pipes or terminations
- Faulty fan wiring connections
- Faulty fan
- Blown fuse F2
How to fix it — step by step
- Record the fault before resetting: write down 'Fan Speed Low / High' exactly as shown on the SMART SYSTEM display, and note that most Knight lockouts need a manual reset with the RESET button on the SMART SYSTEM display after the condition is corrected.
- Safety: shut the boiler down, isolate power and close the gas shut-off valve before opening the cabinet or testing wiring. Gas pressure, gas valve and combustion checks are qualified technician work.
- Locate the parts: the combustion fan is inside the cabinet, its wiring runs to the main control board, fuse F2 is on the control board, and the fault is read on the SMART SYSTEM display.
- Test: confirm the vent and air intake lengths are within the allowed maximum and clear any obstruction at the pipes or terminations. Then check the wiring connections at the fan and at the main control board, and check fuse F2 on the control board.
- End at the fix: clear the venting fault or replace fuse F2 if blown, then press RESET on the SMART SYSTEM display. Wiring sound and venting proven with the speed still wrong pinpoints the fan, and after the fan the main control board.
Did that fix it?
Worked through the steps? Say where you landed - it pinpoints what to do next.
Good - you're done. If it comes back, the causes at the top of this page are where to look first.
This fault usually needs a technician - but this is the part they would test first.
Then the likely broken part is the Fan.
Also tied to this fault: Main control board - Shop at Amazon; Fuse F2 - Shop at Amazon
Parts that commonly fix it
- FanShop at Amazon
- Main control boardShop at Amazon
- Fuse F2Shop at Amazon
What fixed yours?
Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.
Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.
Manual & model number
Find your model number on the rating plate on the boiler jacket, often behind the front panel. It's the key to the right manual pages and the right parts.
Related Lochinvar Boiler Knight 81-286 (SMART SYSTEM) problems
- Fatal Error
- Flame Fail Ign
- Flame Sequence
- Flow Switch/LWCO
- Flue Sensor Fault
- Flue Temp Diff
- Flue Temp High
- Flue Temp Limit
- Gas Pressure SW
- GV/Relay Fail
- Inlet Sensor Fault
- Louver Proving Sw
See all Lochinvar Knight 81-286 (SMART SYSTEM) codes & guides →