Lochinvar Boiler Knight 81-286 (SMART SYSTEM) Delta T High

What this problem usually means

Delta T High is raised when the temperature rise across the heat exchanger has exceeded the set parameters for the boiler. Excessive rise means water is moving too slowly for the heat being added, so the checks are water side: system full and purged, correct piping, and a boiler pump that runs, at the proper speed and size.

Likely causes

  1. Temperature rise across the heat exchanger exceeded set parameters
  2. System not full of water or air not purged
  3. Boiler piped incorrectly
  4. Boiler pump not running, wrong speed or wrong size

How to fix it — step by step

  1. Record the fault before resetting: write down 'Delta T High' exactly as shown on the SMART SYSTEM display, and note that most Knight lockouts need a manual reset with the RESET button on the SMART SYSTEM display after the condition is corrected.
  2. Safety: shut the boiler down, isolate power and close the gas shut-off valve before opening the cabinet or testing wiring. Gas pressure, gas valve and combustion checks are qualified technician work.
  3. Locate the parts: the boiler pump is in the boiler loop piping, the inlet and outlet sensors that measure the rise are in the boiler waterways, and the fault is read on the SMART SYSTEM display.
  4. Test: verify the system is full of water with all air purged and that the boiler is piped properly into the heating system. Check for 120 vac to the boiler pump motor on a call for heat: missing voltage sends the check back to the main control board, and voltage with a stopped pump condemns the pump, after which pump speed and sizing are verified.
  5. End at the fix: restore flow, replace the pump or control board as the voltage test condemns, or correct the pump speed or size, then reset. A proven pump and full, purged system with the fault returning is a technician piping and flow investigation.

Did that fix it?

Worked through the steps? Say where you landed - it pinpoints what to do next.

Parts that commonly fix it

What fixed yours?

Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.

Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.

Manual & model number

Find your model number on the rating plate on the boiler jacket, often behind the front panel. It's the key to the right manual pages and the right parts.