Lochinvar Boiler Knight 81-286 (SMART SYSTEM) Rem Ctrl Flt

What this problem usually means

Rem Ctrl Flt is raised when the external control is cycling too often. The boiler is reporting the behaviour of the control calling it, not an internal failure. The checks are the external control's set point, the wiring between the external control and the unit, and the external control itself.

Likely causes

  1. External control cycling too often
  2. External control set point fault
  3. Wiring fault between the external control and the unit
  4. Faulty external control

How to fix it — step by step

  1. Record the fault before resetting: write down 'Rem Ctrl Flt' exactly as shown on the SMART SYSTEM display, and note that most Knight lockouts need a manual reset with the RESET button on the SMART SYSTEM display after the condition is corrected.
  2. Safety: shut the boiler down, isolate power and close the gas shut-off valve before opening the cabinet or testing wiring. Gas pressure, gas valve and combustion checks are qualified technician work.
  3. Locate the parts: the external control is the thermostat or building control calling the boiler, its wiring lands on the boiler's control inputs, and the fault is read on the SMART SYSTEM display.
  4. Test: check the set point of the external control and watch its call pattern over a heating cycle. Then check the wiring between the external control and the unit for damage or loose terminals; a control that cycles rapidly on its own bench behaviour is itself the pinpoint.
  5. End at the fix: correct the external control set point or wiring, or replace the external control, then reset. No boiler part is replaced for this fault until the external control is proven good. → Shop the external control at Amazon

Did that fix it?

Worked through the steps? Say where you landed - it pinpoints what to do next.

Parts that commonly fix it

What fixed yours?

Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.

Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.

Manual & model number

Find your model number on the rating plate on the boiler jacket, often behind the front panel. It's the key to the right manual pages and the right parts.