Lochinvar Boiler Knight 81-286 (SMART SYSTEM) Sensor Shorted
What this problem usually means
Sensor Shorted is a manual reset lockout raised when either the inlet water or outlet water temperature sensor has been shorted. It is the mirror of Sensor Open: the reading is present but impossible, so the control locks out. Sensor resistance against the manual's tables separates a shorted sensor from shorted wiring.
Likely causes
- Inlet water temperature sensor shorted
- Outlet water temperature sensor shorted
- Shorted sensor wiring
How to fix it — step by step
- Record the fault before resetting: write down 'Sensor Shorted' exactly as shown on the SMART SYSTEM display, and note that most Knight lockouts need a manual reset with the RESET button on the SMART SYSTEM display after the condition is corrected.
- Safety: shut the boiler down, isolate power and close the gas shut-off valve before opening the cabinet or testing wiring. Gas pressure, gas valve and combustion checks are qualified technician work.
- Locate the parts: the inlet and outlet water temperature sensors sit in the boiler waterways, wired to the main control board, and the fault is read on the SMART SYSTEM display.
- Test: check the sensors and their associated wiring and repair or replace anything damaged. Measure the resistance of each sensor and compare it with the tables on page 35 of the service manual; a near zero reading at the sensor itself condemns the sensor, while a good sensor reading puts the short in the wiring.
- End at the fix: replace the shorted sensor or repair the shorted wiring, then press RESET on the SMART SYSTEM display.
Did that fix it?
Worked through the steps? Say where you landed - it pinpoints what to do next.
Good - you're done. If it comes back, the causes at the top of this page are where to look first.
This fault usually needs a technician - but this is the part they would test first.
Then the likely broken part is the Inlet water temperature sensor.
Shop the Inlet water temperature sensor at Amazon
Also tied to this fault: Outlet water temperature sensor - Shop at Amazon
Parts that commonly fix it
- Inlet water temperature sensor$25–$80Shop at Amazon
- Outlet water temperature sensor$25–$80Shop at Amazon
Typical ranges, checked Nov 2026. Your model’s exact part can land outside them.
What fixed yours?
Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.
Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.
Manual & model number
Find your model number on the rating plate on the boiler jacket, often behind the front panel. It's the key to the right manual pages and the right parts.
Related Lochinvar Boiler Knight 81-286 (SMART SYSTEM) problems
- Service Blk
- Anti-cycling
- APS / HEX Temp Sw Open
- Blocked Drain SW
- Delta T High
- Fan Speed Low / High
- Fatal Error
- Flame Fail Ign
- Flame Sequence
- Flow Switch/LWCO
- Flue Sensor Fault
- Flue Temp Diff
See all Lochinvar Knight 81-286 (SMART SYSTEM) codes & guides →