Lochinvar Boiler Knight 81-286 (SMART SYSTEM) Sensor Shorted

What this problem usually means

Sensor Shorted is a manual reset lockout raised when either the inlet water or outlet water temperature sensor has been shorted. It is the mirror of Sensor Open: the reading is present but impossible, so the control locks out. Sensor resistance against the manual's tables separates a shorted sensor from shorted wiring.

Likely causes

  1. Inlet water temperature sensor shorted
  2. Outlet water temperature sensor shorted
  3. Shorted sensor wiring

How to fix it — step by step

  1. Record the fault before resetting: write down 'Sensor Shorted' exactly as shown on the SMART SYSTEM display, and note that most Knight lockouts need a manual reset with the RESET button on the SMART SYSTEM display after the condition is corrected.
  2. Safety: shut the boiler down, isolate power and close the gas shut-off valve before opening the cabinet or testing wiring. Gas pressure, gas valve and combustion checks are qualified technician work.
  3. Locate the parts: the inlet and outlet water temperature sensors sit in the boiler waterways, wired to the main control board, and the fault is read on the SMART SYSTEM display.
  4. Test: check the sensors and their associated wiring and repair or replace anything damaged. Measure the resistance of each sensor and compare it with the tables on page 35 of the service manual; a near zero reading at the sensor itself condemns the sensor, while a good sensor reading puts the short in the wiring.
  5. End at the fix: replace the shorted sensor or repair the shorted wiring, then press RESET on the SMART SYSTEM display.

Did that fix it?

Worked through the steps? Say where you landed - it pinpoints what to do next.

Parts that commonly fix it

Parts run $25–$80

Typical ranges, checked Nov 2026. Your model’s exact part can land outside them.

What fixed yours?

Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.

Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.

Manual & model number

Find your model number on the rating plate on the boiler jacket, often behind the front panel. It's the key to the right manual pages and the right parts.

Related Lochinvar Boiler Knight 81-286 (SMART SYSTEM) problems

See all Lochinvar Knight 81-286 (SMART SYSTEM) codes & guides →