Lochinvar Boiler Knight 81-286 (SMART SYSTEM) Outlet MRHL
What this problem usually means
Outlet MRHL is a manual reset lockout raised when the outlet water temperature has exceeded the setting of the manual reset high limit. It shares the water side checks with the auto reset limit, full system, air purged, correct piping and a running pump, and adds the manual limit itself: its setting, the water sensor resistance, and the limit device. Its set point can be raised to a maximum of 210°F where the application allows.
Likely causes
- Outlet temperature exceeded the manual reset high limit setting
- Air in the system or system not full of water
- Boiler piped incorrectly
- Boiler pump not running
- Faulty manual reset high limit or water sensor
How to fix it — step by step
- Record the fault before resetting: write down 'Outlet MRHL' exactly as shown on the SMART SYSTEM display, and note that most Knight lockouts need a manual reset with the RESET button on the SMART SYSTEM display after the condition is corrected.
- Safety: shut the boiler down, isolate power and close the gas shut-off valve before opening the cabinet or testing wiring. Gas pressure, gas valve and combustion checks are qualified technician work.
- Locate the parts: the manual reset high limit is on the boiler outlet, the water temperature sensors are in the inlet and outlet waterways, the boiler pump is in the boiler loop, and the fault is read on the SMART SYSTEM display.
- Test: verify the system is full and purged and piped properly, then check 120 vac to the boiler pump on a call for heat and work back to the main control board if it is missing. Check the resistance of the water sensors against the sensor table and replace a sensor that reads out of range, and check the setting of the manual reset device itself if it has tripped.
- End at the fix: correct the pinpointed cause, replace a failed sensor, pump, board or high limit as the tests condemn, adjust the manual limit set point up to the 210°F maximum only where appropriate, then press RESET on the SMART SYSTEM display.
Did that fix it?
Worked through the steps? Say where you landed - it pinpoints what to do next.
Good - you're done. If it comes back, the causes at the top of this page are where to look first.
This fault usually needs a technician - but this is the part they would test first.
Then the likely broken part is the Manual reset high limit.
Shop the Manual reset high limit at Amazon
Also tied to this fault: Water temperature sensor - Shop at Amazon; Boiler pump - Shop at Amazon; Main control board - Shop at Amazon
Parts that commonly fix it
- Manual reset high limitShop at Amazon
- Water temperature sensor$25–$80Shop at Amazon
- Boiler pumpShop at Amazon
- Main control boardShop at Amazon
Typical ranges, checked Nov 2026. Your model’s exact part can land outside them.
What fixed yours?
Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.
Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.
Manual & model number
Find your model number on the rating plate on the boiler jacket, often behind the front panel. It's the key to the right manual pages and the right parts.
Related Lochinvar Boiler Knight 81-286 (SMART SYSTEM) problems
- Outlet Sensor Fault
- Outlet Temp Diff
- Outlet Temp High
- Parameters Progr
- Rem Ctrl Flt
- Sensor Open
- Sensor Shorted
- Service Blk
- Anti-cycling
- APS / HEX Temp Sw Open
- Blocked Drain SW
- Delta T High
See all Lochinvar Knight 81-286 (SMART SYSTEM) codes & guides →