Lochinvar Boiler Knight 81-286 (SMART SYSTEM) Outlet ARHL
What this problem usually means
Outlet ARHL means the outlet water temperature has exceeded the setting of the automatic reset high limit. The boiler got too hot at its outlet, which is normally a water side problem: the system must be full, air free, piped properly and actually pumped. The auto reset limit setting itself can be raised to a maximum of 200°F where the application allows.
Likely causes
- Outlet temperature exceeded the automatic reset high limit setting
- Air in the system or system not full of water
- Boiler piped incorrectly
- Boiler pump not running
- High limit set too low for the application
How to fix it — step by step
- Record the fault before resetting: write down 'Outlet ARHL' exactly as shown on the SMART SYSTEM display, and note that most Knight lockouts need a manual reset with the RESET button on the SMART SYSTEM display after the condition is corrected.
- Safety: shut the boiler down, isolate power and close the gas shut-off valve before opening the cabinet or testing wiring. Gas pressure, gas valve and combustion checks are qualified technician work.
- Locate the parts: the automatic reset high limit is on the boiler outlet, the boiler pump is in the boiler loop piping, and the fault is read on the SMART SYSTEM display.
- Test: verify the system is full of water and all air is purged, and verify the boiler is piped properly into the heating system. Check for 120 vac to the boiler pump motor on a call for heat: no voltage sends the check back through the wiring to the main control board, and voltage present with a silent pump condemns the pump.
- End at the fix: correct the water, piping or pump fault, or adjust the auto reset limit set point higher up to the 200°F maximum where appropriate, and the limit resets automatically. A board that never powers the pump is replaced.
Did that fix it?
Worked through the steps? Say where you landed - it pinpoints what to do next.
Good - you're done. If it comes back, the causes at the top of this page are where to look first.
This fault usually needs a technician - but this is the part they would test first.
Then the likely broken part is the Boiler pump.
Shop the Boiler pump at Amazon
Also tied to this fault: Main control board - Shop at Amazon; Automatic reset high limit - Shop at Amazon
Parts that commonly fix it
- Boiler pumpShop at Amazon
- Main control boardShop at Amazon
- Automatic reset high limitShop at Amazon
What fixed yours?
Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.
Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.
Manual & model number
Find your model number on the rating plate on the boiler jacket, often behind the front panel. It's the key to the right manual pages and the right parts.
Related Lochinvar Boiler Knight 81-286 (SMART SYSTEM) problems
- Outlet MRHL
- Outlet Sensor Fault
- Outlet Temp Diff
- Outlet Temp High
- Parameters Progr
- Rem Ctrl Flt
- Sensor Open
- Sensor Shorted
- Service Blk
- Anti-cycling
- APS / HEX Temp Sw Open
- Blocked Drain SW
See all Lochinvar Knight 81-286 (SMART SYSTEM) codes & guides →