Goodman Heat pump ComfortBridge heat pump condensing units H8 Error Code

What the H8 code means

Read on the integrated control module's 7-segment LED display behind the outdoor unit's control access panel (first digit blank), this is the chart's 'High Line Voltage' fault. The manual notes the system may appear to be operating normally, though the compressor protector may be open (compressor and outdoor fan off), and states the control detects line voltage greater than 255 VAC; the fault clears if line voltage decreases below 255 VAC. The listed cause is simply high line voltage, and the corrective actions are to correct the high line voltage condition, contacting the local utility if needed, and verify the unit is connected to the power supply specified on the rating plate.

Likely causes

  1. High line voltage from the utility supply (above 255 VAC)
  2. Unit connected to a power supply other than that on the rating plate

How to fix it — step by step

  1. Record the code before cycling power: remove the outdoor unit's control-box access panel and read all three 7-segment LED digits on the integrated control module (the chart prints the first digit as BLANK), and also use the RECALL push button in Standby (no thermostat demand, press 2-5 seconds) to note the six most recent faults, so H8 is not lost when power is cycled.
  2. Safety: switch the thermostat off, open the outdoor disconnect and the breaker, verify 0 VAC line-to-line and line-to-ground at the contactor with a meter before touching wiring, and treat the run capacitor as charged - discharge it through a resistor and re-verify 0 V before handling it.
  3. Locate the part: there is no failed part in the unit to locate - the measurement is taken at the contactor/line-voltage terminals in the outdoor unit's control box, behind the control access panel where H8 is read, and compared with the rating plate on the unit cabinet.
  4. Test: with a heating/cooling demand present, carefully measure line-to-line voltage at the contactor (live-line-voltage measurement - if you are not qualified for it, stop here and call a technician): a sustained reading above 255 VAC confirms the chart's condition and proves the supply, not the heat pump, is at fault; voltage at or below 255 VAC with H8 persisting points back to the control's voltage sensing.
  5. End at the pinpoint: if voltage is genuinely above 255 VAC, the pinpointed cause is the supply - correct it or contact the local utility, and do not keep resetting the unit; if supply voltage is proven normal, replace the Control board whose sensing is misreporting it. → Shop the control board at Amazon

Did that fix it?

Worked through the steps? Say where you landed - it pinpoints what to do next.

Parts that commonly fix the H8 code

  • Control boardShop at Amazon
  • Tools for this job, if you need them$15–$65

What fixed yours?

Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.

Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.

Manufacturer documentation

Manual & model number

Working on a specific model? The official Goodman manual is on Goodman's support site — you'll need your model number.

Find your model number on the outdoor unit's rating plate. It's the key to the right manual pages and the right parts.

Related Goodman Heat pump ComfortBridge heat pump condensing units error codes

See all Goodman ComfortBridge heat pump condensing units codes & guides →