Goodman Heat pump ComfortBridge heat pump condensing units L8 Error Code

What the L8 code means

Read on the integrated control module's 7-segment LED display behind the outdoor unit's control access panel (first digit blank), this is the chart's low/no line voltage fault - the extracted chart prints both 'Low Line Voltage' and 'No Line Voltage' against L8. The manual notes the system may appear to be operating normally, though the compressor protector may be open (compressor and outdoor fan off), and states the control detects line voltage less than 185 VAC; the fault clears if line voltage increases above 185 VAC. Corrective actions are to check circuit breakers and fuses, verify the unit is connected to the power supply specified on the rating plate, and correct the low line voltage condition, contacting the local utility if needed.

Likely causes

  1. Low line voltage (below 185 VAC)
  2. No line voltage - breaker tripped or fuse open
  3. Unit connected to the wrong power supply

How to fix it — step by step

  1. Record the code before cycling power: remove the outdoor unit's control-box access panel and read all three 7-segment LED digits on the integrated control module (the chart prints the first digit as BLANK), and also use the RECALL push button in Standby (no thermostat demand, press 2-5 seconds) to note the six most recent faults, so L8 is not lost when power is cycled.
  2. Safety: switch the thermostat off, open the outdoor disconnect and the breaker, verify 0 VAC line-to-line and line-to-ground at the contactor with a meter before touching wiring, and treat the run capacitor as charged - discharge it through a resistor and re-verify 0 V before handling it.
  3. Locate the part: start at the breaker panel and outdoor disconnect, then measure at the contactor in the outdoor unit's control box behind the control access panel, where L8 is read; compare the supply with the unit's rating plate on the cabinet.
  4. Test: measure line-to-line voltage at the contactor - below 185 VAC (or zero) confirms a supply problem, and working back to the disconnect and breaker shows where it is lost: voltage present at the disconnect but absent at the unit pinpoints the intervening wiring, while low voltage at the disconnect itself points to the utility supply. This is live-line-voltage diagnosis - unqualified readers should stop and call a technician.
  5. End at the pinpoint: correct the breaker/fuse/wiring fault found, or contact the local utility for a genuinely low supply, and confirm voltage rises above 185 VAC so L8 clears; if supply voltage is proven normal while L8 persists, the Control board's sensing is the pinpointed cause.

Did that fix it?

Worked through the steps? Say where you landed - it pinpoints what to do next.

Parts that commonly fix the L8 code

  • Control boardShop at Amazon
  • Tools for this job, if you need them$15–$65

What fixed yours?

Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.

Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.

Manufacturer documentation

Manual & model number

Working on a specific model? The official Goodman manual is on Goodman's support site — you'll need your model number.

Find your model number on the outdoor unit's rating plate. It's the key to the right manual pages and the right parts.