Goodman Heat pump ComfortBridge heat pump condensing units L2 Error Code
What the L2 code means
Read on the integrated control module's 7-segment LED display behind the outdoor unit's control access panel (first digit blank), L2 is the chart's 'High Pressure Cut Out Lockout (3 Trips)': the high pressure cut-out has tripped three times, leaving compressor and outdoor fan off with thermostat demand present. The manual lists the same two causes as the single-trip code - a blocked condenser coil or the outdoor fan not running - and the same corrective actions: clean the coil and check the outdoor fan motor, its wiring and its capacitor. Because it is a lockout, the fault must be cleared by cycling 24 VAC to the control after the cause is fixed.
Likely causes
- Blocked / dirty condenser (outdoor) coil
- Outdoor fan not running - failed fan motor
- Outdoor fan motor capacitor failed
- Outdoor fan motor wiring fault
How to fix it — step by step
- Record the code before cycling power: remove the outdoor unit's control-box access panel and read all three 7-segment LED digits on the integrated control module (the chart prints the first digit as BLANK), and also use the RECALL push button in Standby (no thermostat demand, press 2-5 seconds) to note the six most recent faults, so L2 is not lost when power is cycled.
- Safety: switch the thermostat off, open the outdoor disconnect and the breaker, verify 0 VAC line-to-line and line-to-ground at the contactor with a meter before touching wiring, and treat the run capacitor as charged - discharge it through a resistor and re-verify 0 V before handling it.
- Locate the part: the outdoor coil inside the louvered cabinet, the outdoor fan motor under the top grille, and its run capacitor and wiring in the control box behind the control access panel, where L2 is read on the integrated control module.
- Test: inspect the coil for blockage first, then watch the fan on a call - a fan that does not run explains repeated high-pressure trips. With power off and the capacitor safely discharged, measure the capacitor's microfarads against its rating (below rating condemns it) and check motor winding continuity; correct voltage at a motor that will not run, with a good capacitor, condemns the Outdoor fan motor. → Shop the outdoor fan motor at Amazon
- End at the fix: clean the coil or replace the Run capacitor / Outdoor fan motor as condemned, then clear the lockout by cycling 24 VAC to the control and run the system to confirm no further high-pressure trips; if coil and fan are proven good and trips continue, the remaining sealed-system diagnosis is EPA-certified work.
Did that fix it?
Worked through the steps? Say where you landed - it pinpoints what to do next.
Good - you're done. If it comes back, the causes at the top of this page are where to look first.
This fault usually needs a technician - but this is the part they would test first.
Then the likely broken part is the Outdoor fan motor.
Shop the Outdoor fan motor at Amazon
Also tied to this fault: Run capacitor - Shop at Amazon
Parts that commonly fix the L2 code
- Outdoor fan motorShop at Amazon
- Run capacitor$5–$35Shop at Amazon
- Tools for this job, if you need them$15–$65
Typical ranges, checked Nov 2026. Your model’s exact part can land outside them.
What fixed yours?
Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.
Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.
Manual & model number
Working on a specific model? The official Goodman manual is on Goodman's support site — you'll need your model number.
Find your model number on the outdoor unit's rating plate. It's the key to the right manual pages and the right parts.
Related Goodman Heat pump ComfortBridge heat pump condensing units error codes
See all Goodman ComfortBridge heat pump condensing units codes & guides →