Goodman Heat pump ComfortBridge heat pump condensing units 02 Error Code

What the 02 code means

Read on the integrated control module's 7-segment LED display behind the outdoor unit's control access panel (first digit blank), code 02 covers the chart's high-side events: 'High Side Fault' - four consecutive compressor protector trips with average run time between trips greater than 1 minute and less than 15 minutes, with low and high pressure switches closed - and 'High Pressure Cut Out Trip,' where compressor and outdoor fan are off with thermostat demand present. For both, the manual lists only two causes: a blocked condenser coil or the outdoor fan not running, with corrective actions to clean the coil and check the fan motor, its wiring and its capacitor.

Likely causes

  1. Blocked / dirty condenser (outdoor) coil
  2. Outdoor fan not running - failed fan motor
  3. Outdoor fan motor capacitor failed
  4. Outdoor fan motor wiring fault

How to fix it — step by step

  1. Record the code before cycling power: remove the outdoor unit's control-box access panel and read all three 7-segment LED digits on the integrated control module (the chart prints the first digit as BLANK), and also use the RECALL push button in Standby (no thermostat demand, press 2-5 seconds) to note the six most recent faults, so 02 is not lost when power is cycled.
  2. Safety: switch the thermostat off, open the outdoor disconnect and the breaker, verify 0 VAC line-to-line and line-to-ground at the contactor with a meter before touching wiring, and treat the run capacitor as charged - discharge it through a resistor and re-verify 0 V before handling it.
  3. Locate the part: the outdoor coil wraps the inside of the outdoor unit's louvered cabinet, and the outdoor fan motor sits under the top grille driving the fan blade; its run capacitor and wiring are in the control box behind the control access panel, where the code is read.
  4. Test: visually inspect the coil - matted dirt or debris is direct evidence of the blockage. With a call running, observe whether the outdoor fan starts: a fan that hums but will not turn points to its capacitor, which can be confirmed with power off by discharging the capacitor and measuring its microfarads against its rating - a reading well below rating condemns the Run capacitor; a capacitor in spec with correct voltage at the motor condemns the Outdoor fan motor. → Shop the run capacitor at Amazon
  5. End at the fix: clean the condenser coil, or replace the Run capacitor or Outdoor fan motor as the tests condemn, restore power and run a call to confirm pressures stay below the cut-out and 02 does not return; the fault clears after 4 consecutive normal cycles or by cycling 24 VAC to the control.

Did that fix it?

Worked through the steps? Say where you landed - it pinpoints what to do next.

Parts that commonly fix the 02 code

Parts run $5–$35

Typical ranges, checked Nov 2026. Your model’s exact part can land outside them.

What fixed yours?

Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.

Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.

Manufacturer documentation

Manual & model number

Working on a specific model? The official Goodman manual is on Goodman's support site — you'll need your model number.

Find your model number on the outdoor unit's rating plate. It's the key to the right manual pages and the right parts.

Related Goodman Heat pump ComfortBridge heat pump condensing units error codes

See all Goodman ComfortBridge heat pump condensing units codes & guides →