Goodman Heat pump ComfortBridge heat pump condensing units 01 Error Code

What the 01 code means

Read on the integrated control module's 7-segment LED display behind the outdoor unit's control access panel (first digit blank), code 01 covers two related low-side events in the chart: 'Low Side Fault' - four consecutive compressor protector trips with average run time between trips greater than 3 hours, compressor at high speed and outdoor fan at low speed - and 'Low Pressure Cut Out Trip,' where compressor and outdoor fan are off with thermostat demand present. Listed causes are low refrigerant charge, a restriction in the liquid line, indoor blower motor failure, or the indoor thermostat set extremely low.

Likely causes

  1. Low refrigerant charge
  2. Restriction in the liquid line
  3. Indoor blower motor failure
  4. Indoor thermostat set extremely low

How to fix it — step by step

  1. Record the code before cycling power: remove the outdoor unit's control-box access panel and read all three 7-segment LED digits on the integrated control module (the chart prints the first digit as BLANK), and also use the RECALL push button in Standby (no thermostat demand, press 2-5 seconds) to note the six most recent faults, so 01 is not lost when power is cycled.
  2. Safety: switch the thermostat off, open the outdoor disconnect and the breaker, verify 0 VAC line-to-line and line-to-ground at the contactor with a meter before touching wiring, and treat the run capacitor as charged - discharge it through a resistor and re-verify 0 V before handling it.
  3. Locate the part: read the code on the integrated control module in the outdoor control box; the checks then move to the indoor blower at the air handler, the liquid line running between the units, and the refrigerant circuit service ports on the outdoor unit.
  4. Test: first rule out airflow - confirm the indoor blower actually runs on a call and the filter is clean, because a dead blower mimics low charge. Refrigerant-side proof (pressures/charge verification) is gauge work on a sealed system: low suction pressure with the blower proven good confirms the low-side fault is charge or restriction, which is EPA-certified work.
  5. End at the pinpoint: if the blower has failed, repair/replace it and retest; if airflow is proven good, the pinpointed cause is low charge or a liquid-line restriction and the fix - leak repair, restriction removal and recharge - is for an EPA-certified technician only. The fault clears after 30 consecutive normal cycles or by cycling 24 VAC to the control.

Did that fix it?

Worked through the steps? Say where you landed - it pinpoints what to do next.

Parts that commonly fix the 01 code

Parts run $5–$30

Typical ranges, checked Nov 2026. Your model’s exact part can land outside them.

What fixed yours?

Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.

Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.

Manufacturer documentation

Manual & model number

Working on a specific model? The official Goodman manual is on Goodman's support site — you'll need your model number.

Find your model number on the outdoor unit's rating plate. It's the key to the right manual pages and the right parts.

Related Goodman Heat pump ComfortBridge heat pump condensing units error codes

See all Goodman ComfortBridge heat pump condensing units codes & guides →