Goodman Heat pump ComfortBridge heat pump condensing units 03 Error Code
What the 03 code means
Read on the integrated control module's 7-segment LED display behind the outdoor unit's control access panel (first digit blank), this is the chart's 'Short Cycling' fault: run time for the last four cycles is less than 3 minutes each, the compressor protector has not tripped, and the low and high pressure switches are closed. The manual lists an intermittent thermostat demand or a faulty compressor relay, with corrective actions to check the thermostat and thermostat wiring and to check compressor relay operation, replacing the control as needed. It also notes the minimum compressor run time is changed from 30 seconds to 3 minutes under this fault.
Likely causes
- Intermittent thermostat demand
- Loose or faulty thermostat wiring
- Faulty compressor relay on the control board
How to fix it — step by step
- Record the code before cycling power: remove the outdoor unit's control-box access panel and read all three 7-segment LED digits on the integrated control module (the chart prints the first digit as BLANK), and also use the RECALL push button in Standby (no thermostat demand, press 2-5 seconds) to note the six most recent faults, so 03 is not lost when power is cycled.
- Safety: switch the thermostat off, open the outdoor disconnect and the breaker, verify 0 VAC line-to-line and line-to-ground at the contactor with a meter before touching wiring, and treat the run capacitor as charged - discharge it through a resistor and re-verify 0 V before handling it.
- Locate the part: start at the thermostat and its low-voltage wiring run to the indoor and outdoor units; the compressor relay whose operation must be checked is on the integrated control module in the outdoor unit's control box, behind the control access panel where the code is read.
- Test: watch a heating/cooling call and meter the demand signal at the outdoor control - demand that drops out mid-call proves the thermostat/wiring side, while steady demand with the compressor still cutting out in under 3 minutes proves the relay/control side. Check thermostat wire connections for looseness at both ends before condemning anything.
- End at the fix: repair/replace the thermostat or its wiring if demand is intermittent, or replace the Control board if demand is steady but its compressor relay drops the compressor; the fault clears after 4 consecutive normal cycles or by cycling 24 VAC to the control. → Shop the control board at Amazon
Did that fix it?
Worked through the steps? Say where you landed - it pinpoints what to do next.
Good - you're done. If it comes back, the causes at the top of this page are where to look first.
Then the likely broken part is the Control board.
Shop the Control board at Amazon
Also tied to this fault: Contactor - Shop at Amazon
Parts that commonly fix the 03 code
- Control boardShop at Amazon
- Contactor$10–$35Shop at Amazon
Typical ranges, checked Nov 2026. Your model’s exact part can land outside them.
What fixed yours?
Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.
Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.
Manual & model number
Working on a specific model? The official Goodman manual is on Goodman's support site — you'll need your model number.
Find your model number on the outdoor unit's rating plate. It's the key to the right manual pages and the right parts.
Related Goodman Heat pump ComfortBridge heat pump condensing units error codes
See all Goodman ComfortBridge heat pump condensing units codes & guides →