Goodman Heat pump ComfortBridge heat pump condensing units 04 Error Code

What the 04 code means

Read on the integrated control module's 7-segment LED display behind the outdoor unit's control access panel (first digit blank), this is the chart's 'Locked Rotor' fault: the compressor protector trips four consecutive times with average run time between trips of less than 15 seconds, and compressor and outdoor fan are off. The manual lists seized compressor bearings, a failed compressor run capacitor, faulty run capacitor wiring, or low line voltage. Its corrective actions are to check compressor operation, check and replace the run capacitor as needed, check the wiring, and verify line voltage is within the range on the rating plate.

Likely causes

  1. Compressor bearings seized (locked rotor)
  2. Failed compressor run capacitor
  3. Faulty run capacitor wiring
  4. Low line voltage

How to fix it — step by step

  1. Record the code before cycling power: remove the outdoor unit's control-box access panel and read all three 7-segment LED digits on the integrated control module (the chart prints the first digit as BLANK), and also use the RECALL push button in Standby (no thermostat demand, press 2-5 seconds) to note the six most recent faults, so 04 is not lost when power is cycled.
  2. Safety: switch the thermostat off, open the outdoor disconnect and the breaker, verify 0 VAC line-to-line and line-to-ground at the contactor with a meter before touching wiring, and treat the run capacitor as charged - discharge it through a resistor and re-verify 0 V before handling it.
  3. Locate the part: the run capacitor is in the outdoor unit's control box behind the control access panel (where the code is read); the compressor sits in the base of the outdoor unit under its access panels, and line voltage is measured at the contactor in the same control box.
  4. Test: measure line voltage at the contactor and compare it with the rating plate - voltage in range removes the utility cause. With power off, discharge the run capacitor and measure its microfarads against its rating: a capacitor far below rating explains a compressor that cannot start and is replaced first; a good capacitor, good wiring and correct voltage with the compressor still tripping its protector in under 15 seconds proves the compressor itself is locked.
  5. End at the pinpoint: replace the Run capacitor if it tests bad and retest; if the compressor is proven locked/seized, that is the pinpointed cause and compressor replacement on the sealed system is EPA-certified technician work only. The fault must be cleared by cycling 24 VAC to the control. → Shop the run capacitor at Amazon

Did that fix it?

Worked through the steps? Say where you landed - it pinpoints what to do next.

Parts that commonly fix the 04 code

Parts run $5–$35
  • Run capacitor$5–$35Shop at Amazon
  • Tools for this job, if you need them$15–$65

Typical ranges, checked Nov 2026. Your model’s exact part can land outside them.

What fixed yours?

Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.

Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.

Manufacturer documentation

Manual & model number

Working on a specific model? The official Goodman manual is on Goodman's support site — you'll need your model number.

Find your model number on the outdoor unit's rating plate. It's the key to the right manual pages and the right parts.

Related Goodman Heat pump ComfortBridge heat pump condensing units error codes

See all Goodman ComfortBridge heat pump condensing units codes & guides →