Crown Boiler Boiler Common Problems
Find your problem in the list below. Each page explains the most likely causes, step-by-step checks you can do yourself, when to call a pro, and the parts that commonly resolve it. 32 problems covered.
Finding your model number: it is on the rating plate on the boiler jacket, often behind the front panel.
Tap any code for its full fix — causes, step-by-step checks, and the parts that commonly fix it.
Aruba 5 (numeric error codes)
The Aruba 5 installation manual's Table 13.0 lists numeric error codes with a meaning and possible causes for each.
| Code | What it means | Check first | |
|---|---|---|---|
| 18 | Error 18 is an internal electronics failure in the boiler control. The manual's direction is direct: cycle… | Internal problem with the boiler control | › |
| 23 | Error 23 means flame was sensed during the 1.7 second pre-purge, before the pilot valve opened. Flame proof… | Defective gas valve | › |
| 32 | Error 32 is a boiler water temperature sensor failure. The control cannot trust the water temperature… | Loose sensor connection at the control | › |
| 4 | Error 4 is a low flame signal. The pilot lit but the flame proof reaching the control is too weak to trust… | Low gas pressure at the gas valve inlet | › |
| 55 | Error 55 means the vent damper failed to open after 60 seconds. The boiler will not fire with the damper… | Loose or defective damper harness | › |
| 56 | Error 56 means power is present at the end of the limit string when it should not be. The manual names the… | Defective boiler control | › |
| 57 | Error 57 is a grounded pilot electrode. Something is shorting the pilot electrode to ground: condensate or… | Condensate or foreign material shorting the pilot electrode to ground | › |
| 58 | Error 58 is an AC power frequency error. The control expects a 60 Hz supply and is not seeing it, or the… | 120 VAC supply frequency incorrect (should be 60 Hz) | › |
| 59 | Error 59 is a line voltage error: the supply voltage is too high or too low. The boiler wants 120 VAC… | Power supply voltage incorrect (should be 120 VAC nominal) | › |
| 6 | Error 6 means a pilot flame was detected when no flame should be present. The control sees flame proof with… | Defective gas valve leaking gas through | › |
| 60 | Error 60 means the thermostat input is higher than its threshold. External voltage is being applied to the… | External voltage applied to the thermostat connections | › |
| 61 | Error 61 is an unstable line voltage. The incoming 120 VAC supply is dirty or swinging, loose connections… | Dirty 120 VAC power supply | › |
| 63 | Error 63 means maximum recycles were exceeded: the boiler lost proof of pilot six times in a row, the same… | Repeated loss of pilot proof (see Error 4 causes) | › |
| 64 | Error 64 is an internal failure code tied to the damper and pilot checks. The manual lists a loose or… | Loose or defective damper harness | › |
| 89 | Error 89 means EnviraCom communication has been lost between the boiler control and certain Crown control… | Communication lost between the boiler control and a Crown control option | › |
Phantom-X (soft + hard lockouts)
The Phantom-X control splits its faults into a soft lockout table and a hard lockout table; the entries carry the table name because the bare numbers repeat across the two tables and collide with the Aruba codes.
| Problem | What it means | Check first | |
|---|---|---|---|
| Hard Lockout 12 | Phantom-X hard lockout 12 means a flame signal was present when there should be no flame: flame detected out… | Flame signal present with no flame expected | › |
| Hard Lockout 18 | Phantom-X hard lockout 18 means light-off rate proving failed: the blower is not running at light-off rate… | Loose connection in 120 VAC blower wiring | › |
| Hard Lockout 23 | Phantom-X hard lockout 23 means the R7910 control's 24 VAC control power is high or low. The manual's causes… | 24 VAC control power high or low | › |
| Hard Lockout 27 | Phantom-X hard lockout 27 is ignition failure on the larger models: on model PHNTM500, flame failure after 1… | No gas pressure, or pressure under the rating-plate minimum | › |
| Hard Lockout 4 | Phantom-X hard lockout 4 is Supply High Limit: the R7910 supply sensor detected temperatures in excess of 200… | Heating load far below the boiler minimum firing rate | › |
| Hard Lockout 6 | Phantom-X hard lockout 6 is Stack High Limit: the R7910 flue gas (stack) sensor detected temperatures in… | Stack temperature above 572 F (300 C) | › |
| Soft Lockout 10 | Phantom-X soft lockout 10 is a stack sensor fault: the flue gas (stack) temperature sensor is shorted or… | Shorted or open stack (flue gas) temperature sensor | › |
| Soft Lockout 11 | Phantom-X soft lockout 11 is ignition failure: on model PH170, flame failure after 3 tries to restart (the… | No gas pressure, or pressure under the rating-plate minimum | › |
| Soft Lockout 13 | Phantom-X soft lockout 13 means the flame rod is shorted to ground. The control sees a grounded flame rod and… | Flame rod shorted to ground | › |
| Soft Lockout 14 | Phantom-X soft lockout 14 is DT inlet/outlet high: the temperature rise between supply and return is too… | Inadequate boiler water flow | › |
| Soft Lockout 15 | Phantom-X soft lockout 15 means the control is reading a return sensor temperature higher than the supply… | Return temperature higher than supply for at least 60 seconds | › |
| Soft Lockout 16 | Phantom-X soft lockout 16 means the supply water temperature has risen too quickly. The manual ties it to the… | Supply temperature rising too quickly | › |
| Soft Lockout 2 | Phantom-X soft lockout 2 means a Boiler Safety Limit wired to the control has opened. The manual groups the… | Condensate trap float switch contact open (plugged condensate trap) | › |
| Soft Lockout 3 | Phantom-X soft lockout 3 means the Boiler Safety Limit or External Limit circuit wired to terminals J5-1 (and… | External limit device open or defective | › |
| Soft Lockout 7 | Phantom-X soft lockout 7 is a return sensor fault: the return temperature sensor is shorted or open. The… | Shorted or open return temperature sensor | › |
| Soft Lockout 8 | Phantom-X soft lockout 8 is a supply sensor fault: the supply temperature sensor is shorted or open. Supply… | Shorted or open supply temperature sensor | › |
| Soft Lockout 9 | Phantom-X soft lockout 9 is a DHW sensor fault: the domestic hot water temperature sensor is shorted or open.… | Shorted or open DHW temperature sensor | › |
Common questions
Where do I find a Crown Aruba 5 error code's meaning?
In Table 13.0 of the Aruba 5 installation manual - each numeric code carries its meaning and possible causes. Error 56's entry even gives the manual's own electrical test: 24 VAC measured at the P6-5 terminal.
Once you know the part you need, browse Crown Boiler Boiler replacement parts → The parts shelves are organized by brand, with the parts that actually fix these codes.