Crown Boiler Boiler Common Problems

Find your problem in the list below. Each page explains the most likely causes, step-by-step checks you can do yourself, when to call a pro, and the parts that commonly resolve it. 32 problems covered.

Finding your model number: it is on the rating plate on the boiler jacket, often behind the front panel.

Tap any code for its full fix — causes, step-by-step checks, and the parts that commonly fix it.

Aruba 5 (numeric error codes)

The Aruba 5 installation manual's Table 13.0 lists numeric error codes with a meaning and possible causes for each.

CodeWhat it meansCheck first
18Error 18 is an internal electronics failure in the boiler control. The manual's direction is direct: cycle…Internal problem with the boiler control›
23Error 23 means flame was sensed during the 1.7 second pre-purge, before the pilot valve opened. Flame proof…Defective gas valve›
32Error 32 is a boiler water temperature sensor failure. The control cannot trust the water temperature…Loose sensor connection at the control›
4Error 4 is a low flame signal. The pilot lit but the flame proof reaching the control is too weak to trust…Low gas pressure at the gas valve inlet›
55Error 55 means the vent damper failed to open after 60 seconds. The boiler will not fire with the damper…Loose or defective damper harness›
56Error 56 means power is present at the end of the limit string when it should not be. The manual names the…Defective boiler control›
57Error 57 is a grounded pilot electrode. Something is shorting the pilot electrode to ground: condensate or…Condensate or foreign material shorting the pilot electrode to ground›
58Error 58 is an AC power frequency error. The control expects a 60 Hz supply and is not seeing it, or the…120 VAC supply frequency incorrect (should be 60 Hz)›
59Error 59 is a line voltage error: the supply voltage is too high or too low. The boiler wants 120 VAC…Power supply voltage incorrect (should be 120 VAC nominal)›
6Error 6 means a pilot flame was detected when no flame should be present. The control sees flame proof with…Defective gas valve leaking gas through›
60Error 60 means the thermostat input is higher than its threshold. External voltage is being applied to the…External voltage applied to the thermostat connections›
61Error 61 is an unstable line voltage. The incoming 120 VAC supply is dirty or swinging, loose connections…Dirty 120 VAC power supply›
63Error 63 means maximum recycles were exceeded: the boiler lost proof of pilot six times in a row, the same…Repeated loss of pilot proof (see Error 4 causes)›
64Error 64 is an internal failure code tied to the damper and pilot checks. The manual lists a loose or…Loose or defective damper harness›
89Error 89 means EnviraCom communication has been lost between the boiler control and certain Crown control…Communication lost between the boiler control and a Crown control option›

Phantom-X (soft + hard lockouts)

The Phantom-X control splits its faults into a soft lockout table and a hard lockout table; the entries carry the table name because the bare numbers repeat across the two tables and collide with the Aruba codes.

ProblemWhat it meansCheck first
Hard Lockout 12Phantom-X hard lockout 12 means a flame signal was present when there should be no flame: flame detected out…Flame signal present with no flame expected›
Hard Lockout 18Phantom-X hard lockout 18 means light-off rate proving failed: the blower is not running at light-off rate…Loose connection in 120 VAC blower wiring›
Hard Lockout 23Phantom-X hard lockout 23 means the R7910 control's 24 VAC control power is high or low. The manual's causes…24 VAC control power high or low›
Hard Lockout 27Phantom-X hard lockout 27 is ignition failure on the larger models: on model PHNTM500, flame failure after 1…No gas pressure, or pressure under the rating-plate minimum›
Hard Lockout 4Phantom-X hard lockout 4 is Supply High Limit: the R7910 supply sensor detected temperatures in excess of 200…Heating load far below the boiler minimum firing rate›
Hard Lockout 6Phantom-X hard lockout 6 is Stack High Limit: the R7910 flue gas (stack) sensor detected temperatures in…Stack temperature above 572 F (300 C)›
Soft Lockout 10Phantom-X soft lockout 10 is a stack sensor fault: the flue gas (stack) temperature sensor is shorted or…Shorted or open stack (flue gas) temperature sensor›
Soft Lockout 11Phantom-X soft lockout 11 is ignition failure: on model PH170, flame failure after 3 tries to restart (the…No gas pressure, or pressure under the rating-plate minimum›
Soft Lockout 13Phantom-X soft lockout 13 means the flame rod is shorted to ground. The control sees a grounded flame rod and…Flame rod shorted to ground›
Soft Lockout 14Phantom-X soft lockout 14 is DT inlet/outlet high: the temperature rise between supply and return is too…Inadequate boiler water flow›
Soft Lockout 15Phantom-X soft lockout 15 means the control is reading a return sensor temperature higher than the supply…Return temperature higher than supply for at least 60 seconds›
Soft Lockout 16Phantom-X soft lockout 16 means the supply water temperature has risen too quickly. The manual ties it to the…Supply temperature rising too quickly›
Soft Lockout 2Phantom-X soft lockout 2 means a Boiler Safety Limit wired to the control has opened. The manual groups the…Condensate trap float switch contact open (plugged condensate trap)›
Soft Lockout 3Phantom-X soft lockout 3 means the Boiler Safety Limit or External Limit circuit wired to terminals J5-1 (and…External limit device open or defective›
Soft Lockout 7Phantom-X soft lockout 7 is a return sensor fault: the return temperature sensor is shorted or open. The…Shorted or open return temperature sensor›
Soft Lockout 8Phantom-X soft lockout 8 is a supply sensor fault: the supply temperature sensor is shorted or open. Supply…Shorted or open supply temperature sensor›
Soft Lockout 9Phantom-X soft lockout 9 is a DHW sensor fault: the domestic hot water temperature sensor is shorted or open.…Shorted or open DHW temperature sensor›

Common questions

Where do I find a Crown Aruba 5 error code's meaning?
In Table 13.0 of the Aruba 5 installation manual - each numeric code carries its meaning and possible causes. Error 56's entry even gives the manual's own electrical test: 24 VAC measured at the P6-5 terminal.

Looking for a part?

Once you know the part you need, browse Crown Boiler Boiler replacement parts → The parts shelves are organized by brand, with the parts that actually fix these codes.