What the 58 code means

Error 58 is an AC power frequency error. The control expects a 60 Hz supply and is not seeing it, or the supply is electrically dirty. The manual also lists a damaged boiler water temperature sensor common wire shorted to ground as a cause, which can fool the control's power sensing.

Likely causes

  1. 120 VAC supply frequency incorrect (should be 60 Hz)
  2. Dirty 120 VAC power supply
  3. Water temperature sensor common (center) wire damaged and shorted to ground

How to fix it — step by step

  1. Record the code before resetting anything: write down the display exactly as shown (58) and whether the boiler was in a heating call, a hot-water call, or idle when it appeared.
  2. Safety: turn the thermostat down, switch off power to the boiler at the service switch and breaker, and close the manual gas shutoff if you smell gas or see scorching. Do not open the burner compartment if you smell gas; leave and call the gas supplier.
  3. Locate the part: start at the boiler's 120 VAC supply connection and the transformer; then inspect the water temperature sensor lead where it runs to the control, especially the center common wire.
  4. Test: have the supply frequency and quality checked (the manual directs you to an electrician or the utility for a dirty supply), and inspect the sensor common wire for damage or a short to ground. A clean supply with a damaged sensor wire explains the code without any utility fault.
  5. End at the pinpoint: correct the power supply problem, or repair the Temperature sensor wiring if the common wire is shorted. Electrical supply work is for an electrician; boiler wiring is technician work.

Did that fix it?

Worked through the steps? Say where you landed - it pinpoints what to do next.

Parts that commonly fix the 58 code

Parts run $25–$80

Typical ranges, checked Nov 2026. Your model’s exact part can land outside them.

What fixed yours?

Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.

Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.

Manual & model number

Find your model number on the rating plate on the boiler jacket, often behind the front panel. It's the key to the right manual pages and the right parts.

Related Crown Boiler Boiler Aruba 5 series error codes

See all Crown Boiler Aruba 5 series codes & guides →