Crown Boiler Boiler Aruba 5 series 56 Error Code
What the 56 code means
Error 56 means power is present at the end of the limit string when it should not be. The manual names the control, the vent damper, or the damper harness as defective. The manual gives an exact test: with Error 56 present and no call for heat, unplug the damper harness from the control and check for 24 VAC between terminal P6-5 on the control and ground.
Likely causes
- Defective boiler control
- Defective vent damper
- Defective or shorted damper harness
How to fix it — step by step
- Record the code before resetting anything: write down the display exactly as shown (56) and whether the boiler was in a heating call, a hot-water call, or idle when it appeared.
- Safety: turn the thermostat down, switch off power to the boiler at the service switch and breaker, and close the manual gas shutoff if you smell gas or see scorching. Do not open the burner compartment if you smell gas; leave and call the gas supplier.
- Locate the part: terminal P6-5 is on the boiler control (see Figure 9.2 in the manual for its location); the damper harness plugs into the control and runs to the vent damper at the flue outlet.
- Test: unplug the damper harness from the control with no call for heat and measure between P6-5 and ground. Voltage present means replace the control; no voltage means inspect the damper harness for shorts or miswired connections, and if the harness is sound, replace the vent damper. → Shop the vent damper at Amazon
- End at the pinpoint: replace the boiler Control, repair the damper harness, or replace the Vent damper, exactly as the P6-5 voltage test directs. Technician work.
Did that fix it?
Worked through the steps? Say where you landed - it pinpoints what to do next.
Good - you're done. If it comes back, the causes at the top of this page are where to look first.
This fault usually needs a technician - but this is the part they would test first.
Then the likely broken part is the Boiler control.
Shop the Boiler control at Amazon
Also tied to this fault: Vent damper - Shop at Amazon
Parts that commonly fix the 56 code
- Boiler controlShop at Amazon
- Vent damperShop at Amazon
- Tools for this job, if you need them$15–$65
What fixed yours?
Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.
Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.
Manual & model number
Find your model number on the rating plate on the boiler jacket, often behind the front panel. It's the key to the right manual pages and the right parts.