Crown Boiler Boiler Phantom-X series (PHNTM) Hard Lockout 4
What this problem usually means
Phantom-X hard lockout 4 is Supply High Limit: the R7910 supply sensor detected temperatures in excess of 200 F. The manual's causes are a heating load far below the boiler's minimum firing rate, a defective system circulator or no flow in the primary loop, a defective boiler circulator or insufficient boiler-loop flow, and a control system miswired so the boiler can run when no zones are calling. A hard lockout needs a manual reset after the cause is fixed.
Likely causes
- Heating load far below the boiler minimum firing rate
- Defective system circulator or no flow in the primary loop
- Defective boiler circulator or insufficient boiler loop flow
- Control system miswired (boiler runs with no zones calling)
How to fix it — step by step
- Record the code before resetting anything: write down the display exactly as shown (Hard Lockout 4) and whether the boiler was in a heating call, a hot-water call, or idle when it appeared.
- Safety: turn the thermostat down, switch off power to the boiler at the service switch and breaker, and close the manual gas shutoff if you smell gas or see scorching. Do not open the burner compartment if you smell gas; leave and call the gas supplier.
- Locate the part: both circulators (system and boiler loop), the flow path through the primary loop, and the zone/control wiring that can call the boiler.
- Test: prove flow in both loops during a call and confirm the boiler only fires with a genuine zone demand. Good flow with a real demand and repeated trips points to the boiler short-cycling against too small a load at minimum fire.
- End at the pinpoint: repair the Circulator or flow fault, or correct the control wiring, as the checks condemn, then reset the lockout manually from the Active Fault display or the R7910 control. Technician work.
Did that fix it?
Worked through the steps? Say where you landed - it pinpoints what to do next.
Good - you're done. If it comes back, the causes at the top of this page are where to look first.
This fault usually needs a technician - but this is the part they would test first.
Then the likely broken part is the Circulator.
Parts that commonly fix it
- CirculatorShop at Amazon
What fixed yours?
Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.
Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.
Manual & model number
Find your model number on the rating plate on the boiler jacket, often behind the front panel. It's the key to the right manual pages and the right parts.
Related Crown Boiler Boiler Phantom-X series (PHNTM) problems
- Hard Lockout 6
- Soft Lockout 10
- Soft Lockout 11
- Soft Lockout 13
- Soft Lockout 14
- Soft Lockout 15
- Soft Lockout 16
- Soft Lockout 2
- Soft Lockout 3
- Soft Lockout 7
- Soft Lockout 8
- Soft Lockout 9
See all Crown Boiler Phantom-X series (PHNTM) codes & guides →