Crown Boiler Phantom-X series (PHNTM) Common Problems
Find your problem in the list below. Each page explains the most likely causes, step-by-step checks you can do yourself, when to call a pro, and the parts that commonly resolve it. 17 problems covered.
Tap any code for its full fix — causes, step-by-step checks, and the parts that commonly fix it.
| Problem | What it means | Check first | |
|---|---|---|---|
| Hard Lockout 12 | Phantom-X hard lockout 12 means a flame signal was present when there should be no flame: flame detected out… | Flame signal present with no flame expected | › |
| Hard Lockout 18 | Phantom-X hard lockout 18 means light-off rate proving failed: the blower is not running at light-off rate… | Loose connection in 120 VAC blower wiring | › |
| Hard Lockout 23 | Phantom-X hard lockout 23 means the R7910 control's 24 VAC control power is high or low. The manual's causes… | 24 VAC control power high or low | › |
| Hard Lockout 27 | Phantom-X hard lockout 27 is ignition failure on the larger models: on model PHNTM500, flame failure after 1… | No gas pressure, or pressure under the rating-plate minimum | › |
| Hard Lockout 4 | Phantom-X hard lockout 4 is Supply High Limit: the R7910 supply sensor detected temperatures in excess of 200… | Heating load far below the boiler minimum firing rate | › |
| Hard Lockout 6 | Phantom-X hard lockout 6 is Stack High Limit: the R7910 flue gas (stack) sensor detected temperatures in… | Stack temperature above 572 F (300 C) | › |
| Soft Lockout 10 | Phantom-X soft lockout 10 is a stack sensor fault: the flue gas (stack) temperature sensor is shorted or… | Shorted or open stack (flue gas) temperature sensor | › |
| Soft Lockout 11 | Phantom-X soft lockout 11 is ignition failure: on model PH170, flame failure after 3 tries to restart (the… | No gas pressure, or pressure under the rating-plate minimum | › |
| Soft Lockout 13 | Phantom-X soft lockout 13 means the flame rod is shorted to ground. The control sees a grounded flame rod and… | Flame rod shorted to ground | › |
| Soft Lockout 14 | Phantom-X soft lockout 14 is DT inlet/outlet high: the temperature rise between supply and return is too… | Inadequate boiler water flow | › |
| Soft Lockout 15 | Phantom-X soft lockout 15 means the control is reading a return sensor temperature higher than the supply… | Return temperature higher than supply for at least 60 seconds | › |
| Soft Lockout 16 | Phantom-X soft lockout 16 means the supply water temperature has risen too quickly. The manual ties it to the… | Supply temperature rising too quickly | › |
| Soft Lockout 2 | Phantom-X soft lockout 2 means a Boiler Safety Limit wired to the control has opened. The manual groups the… | Condensate trap float switch contact open (plugged condensate trap) | › |
| Soft Lockout 3 | Phantom-X soft lockout 3 means the Boiler Safety Limit or External Limit circuit wired to terminals J5-1 (and… | External limit device open or defective | › |
| Soft Lockout 7 | Phantom-X soft lockout 7 is a return sensor fault: the return temperature sensor is shorted or open. The… | Shorted or open return temperature sensor | › |
| Soft Lockout 8 | Phantom-X soft lockout 8 is a supply sensor fault: the supply temperature sensor is shorted or open. Supply… | Shorted or open supply temperature sensor | › |
| Soft Lockout 9 | Phantom-X soft lockout 9 is a DHW sensor fault: the domestic hot water temperature sensor is shorted or open.… | Shorted or open DHW temperature sensor | › |
All Crown Boiler boiler models & codes →