Crown Boiler Boiler Aruba 5 series 4 Error Code

What the 4 code means

Error 4 is a low flame signal. The pilot lit but the flame proof reaching the control is too weak to trust, so the boiler shuts down. Weak gas pressure, a dirty or damaged pilot, and poor electrical connections are the listed causes.

Likely causes

  1. Low gas pressure at the gas valve inlet
  2. Partially plugged pilot tubing or pilot orifice
  3. Loose connection in the ignition cable or ground wiring
  4. Dirty pilot electrode or ground strap
  5. Cracked pilot electrode porcelain or damaged pilot hood
  6. Defective control

How to fix it — step by step

  1. Record the code before resetting anything: write down the display exactly as shown (4) and whether the boiler was in a heating call, a hot-water call, or idle when it appeared.
  2. Safety: turn the thermostat down, switch off power to the boiler at the service switch and breaker, and close the manual gas shutoff if you smell gas or see scorching. Do not open the burner compartment if you smell gas; leave and call the gas supplier.
  3. Locate the part: the pilot assembly and its electrode sit at the main burner inside the burner compartment; the ignition cable runs from the pilot back to the boiler control.
  4. Test: check inlet gas pressure at the valve against the rating plate, then inspect the pilot flame and electrode condition. A strong, steady pilot flame with correct pressure and clean connections that still reads low condemns the control's flame circuit.
  5. End at the pinpoint: clean or replace the Pilot assembly parts condemned (tubing, orifice, electrode), correct the gas pressure, or replace the boiler Control if the pilot and pressure prove good. Gas work is technician work. → Shop the pilot assembly at Amazon → Shop the boiler control at Amazon

Did that fix it?

Worked through the steps? Say where you landed - it pinpoints what to do next.

Parts that commonly fix the 4 code

What fixed yours?

Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.

Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.

Manual & model number

Find your model number on the rating plate on the boiler jacket, often behind the front panel. It's the key to the right manual pages and the right parts.

Related Crown Boiler Boiler Aruba 5 series error codes

See all Crown Boiler Aruba 5 series codes & guides →