Crown Boiler Boiler Phantom-X series (PHNTM) Hard Lockout 27

What this problem usually means

Phantom-X hard lockout 27 is ignition failure on the larger models: on model PHNTM500, flame failure after 1 try to restart. The manual's cause list is the same as the soft-lockout ignition list: no gas pressure, pressure under the rating-plate minimum, an unpurged gas line, a defective electrode, a loose burner ground, a defective ignition cable, a defective gas valve, and an out-of-adjustment air/fuel mixture.

Likely causes

  1. No gas pressure, or pressure under the rating-plate minimum
  2. Gas line not completely purged of air
  3. Defective electrode
  4. Loose burner ground connection
  5. Defective ignition cable
  6. Defective gas valve
  7. Air/fuel mixture out of adjustment

How to fix it — step by step

  1. Record the code before resetting anything: write down the display exactly as shown (Hard Lockout 27) and whether the boiler was in a heating call, a hot-water call, or idle when it appeared.
  2. Safety: turn the thermostat down, switch off power to the boiler at the service switch and breaker, and close the manual gas shutoff if you smell gas or see scorching. Do not open the burner compartment if you smell gas; leave and call the gas supplier.
  3. Locate the part: the electrode and ignition cable at the burner, the gas valve in the front gas train, and the burner ground connection.
  4. Test: confirm gas pressure, then check for 24 VAC at the gas valve harness during the trial for ignition before replacing the valve, per the manual. Work gas, spark, and flame sensing in that order; the failed leg is the pinpoint.
  5. End at the pinpoint: fix the condemned leg (gas supply, Electrode, Ignition cable, ground, or Gas valve), then reset manually from the Active Fault display or the R7910. Technician work only.

Did that fix it?

Worked through the steps? Say where you landed - it pinpoints what to do next.

Parts that commonly fix it

Parts run $100–$355

Typical ranges, checked Nov 2026. Your model’s exact part can land outside them.

What fixed yours?

Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.

Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.