Bosch Buderus Logamax plus GB162 Error Codes
Find your code in the list below. Each page explains what the code means, the most likely causes, step-by-step fixes you can do yourself, and the parts that commonly resolve it. 23 codes covered.
Tap any code for its full fix — causes, step-by-step checks, and the parts that commonly fix it.
| Code | What it means | Check first | |
|---|---|---|---|
| 0Y 276 | Display code 0Y with subdisplay 276 is a blocking fault: the supply temperature sensor has measured a heating… | Supply temperature above 203 F (95 C) | › |
| 0Y 285 | Display code 0Y with subdisplay 285 is a blocking fault: the return temperature sensor has measured a return… | Return temperature above 203 F (95 C) | › |
| 1A 316 | Display code 1A with subdisplay 316 is a locking fault: the flue gas sensor temperature is too high. The… | Flue gas temperature too high | › |
| 1C 210 | Display code 1C with subdisplay 210 is a locking fault: the safety temperature switch has measured an… | Safety temperature switch open on high temperature | › |
| 2E 207 | Display code 2E with subdisplay 207 is a blocking fault: heating system water pressure is too low, under 3… | System water pressure under 3 PSI | › |
| 2F 260 | Display code 2F with subdisplay 260 is a blocking fault: the supply temperature sensor measured no heating… | No water temperature rise after burner start | › |
| 2L 266 | Display code 2L with subdisplay 266 is a locking fault: the pressure sensor failed to measure a pressure… | Pressure sensor failed to detect a pressure rise in four attempts | › |
| 2P 212 | Display code 2P with subdisplay 212 is a blocking fault: the supply temperature sensor measured a heating… | Supply temperature rising faster than 9 F per second | › |
| 2U 213 | Display code 2U with subdisplay 213 is a blocking fault: the temperature difference between the supply… | Supply-to-return difference over 90 F (50 C) | › |
| 3A 264 | Display code 3A with subdisplay 264 is a blocking fault: the fan unit tacho signal failed, or the fan unit… | Fan tacho signal lost during operation | › |
| 3C 217 | Display code 3C with subdisplay 217 is a locking fault: the fan unit is running irregularly while starting… | Fan running irregularly at startup | › |
| 3L 214 | Display code 3L with subdisplay 214 is a locking fault: the fan unit tacho signal or the fan main voltage was… | No fan tacho signal before ignition | › |
| 3P 216 | Display code 3P with subdisplay 216 is a locking fault: the fan unit is running too slowly. A fan that cannot… | Fan running too slowly | › |
| 3Y 215 | Display code 3Y with subdisplay 215 is a locking fault: the fan unit is running too fast. Overspeed means the… | Fan running too fast | › |
| 4A 218 | Display code 4A with subdisplay 218 is a locking fault: the supply temperature sensor measured a heating… | Supply temperature above 221 F (105 C) | › |
| 4C 224 | Display code 4C with subdisplay 224 is a locking fault: the safety temperature switch measured an excessively… | Safety temperature switch open on excess temperature | › |
| 4U 222 | Display code 4U with subdisplay 222 is a locking fault: the contacts of the supply temperature sensor have… | Supply temperature sensor contacts shorted | › |
| 4Y 223 | Display code 4Y with subdisplay 223 is a locking fault: the contacts of the supply temperature sensor are… | Supply temperature sensor contacts open | › |
| 6A 227 | Display code 6A with subdisplay 227 is the GB162 flame fault: insufficient flame activity (ionization… | Insufficient ionization current during ignition attempts | › |
| 6C 228 | Display code 6C with subdisplay 228 is a locking fault: flames (ionization current) were measured after a… | Flame signal present before the gas valve opened | › |
| 6L 229 | Display code 6L with subdisplay 229 is a blocking fault: insufficient flame activity (ionization current) was… | Flame signal lost during the run | › |
| 6P 269 | Display code 6P with subdisplay 269 is a locking fault: the glow ignitor was activated for more than 10… | Glow ignitor activated longer than 10 minutes | › |
| 9L 234 | Display code 9L with subdisplay 234 is a locking fault: the contacts of the gas valve are open. The control… | Gas valve contacts open | › |
All Bosch boiler models & codes →