Bosch Boiler Buderus Logamax plus GB162 2F 260 Error Code

What the 2F 260 code means

Display code 2F with subdisplay 260 is a blocking fault: the supply temperature sensor measured no heating water temperature increase after a burner start. The burner fired but the water at the outlet did not warm, which points to no circulation or a sensor that is not reading the water. The boiler blocks rather than keep firing into still water.

Likely causes

  1. No water temperature rise after burner start
  2. No circulation through the boiler
  3. Supply sensor not in contact with the water flow

How to fix it — step by step

  1. Record the code before resetting anything: write down the display exactly as shown (2F 260) and whether the boiler was in a heating call, a hot-water call, or idle when it appeared.
  2. Safety: turn the thermostat down, switch off power to the boiler at the service switch and breaker, and close the manual gas shutoff if you smell gas or see scorching. Do not open the burner compartment if you smell gas; leave and call the gas supplier.
  3. Locate the part: the supply temperature sensor is on the supply connection at the heat exchanger outlet; the circulator is in the pump group below.
  4. Test: start a heat call and feel the supply pipe a short distance from the boiler. A pipe that warms while the display shows no rise condemns the sensor; a pipe that stays cold with the burner firing condemns circulation.
  5. End at the pinpoint: restore circulation (Circulator repair, open valves, bleed air) or replace the supply Temperature sensor, whichever the pipe test condemns. Technician work. → Shop the temperature sensor at Amazon → Shop the circulator at Amazon

Did that fix it?

Worked through the steps? Say where you landed - it pinpoints what to do next.

Parts that commonly fix the 2F 260 code

Parts run $25–$80

Typical ranges, checked Nov 2026. Your model’s exact part can land outside them.

What fixed yours?

Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.

Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.

Manual & model number

Working on a specific model? The official Bosch manual is on Bosch's support site — you'll need your model number.

Find your model number on the rating plate on the boiler jacket, often behind the front panel. It's the key to the right manual pages and the right parts.