Bosch Boiler Buderus Logamax plus GB162 4A 218 Error Code

What the 4A 218 code means

Display code 4A with subdisplay 218 is a locking fault: the supply temperature sensor measured a heating supply temperature higher than 221 F (105 C). This is the hard overheat lockout for the water leaving the boiler. The boiler stays locked until it cools, the cause is found, and the fault is reset.

Likely causes

  1. Supply temperature above 221 F (105 C)
  2. No or very low water flow at full fire
  3. Circulator failure during a call

How to fix it — step by step

  1. Record the code before resetting anything: write down the display exactly as shown (4A 218) and whether the boiler was in a heating call, a hot-water call, or idle when it appeared.
  2. Safety: turn the thermostat down, switch off power to the boiler at the service switch and breaker, and close the manual gas shutoff if you smell gas or see scorching. Do not open the burner compartment if you smell gas; leave and call the gas supplier.
  3. Locate the part: the supply temperature sensor is at the heat exchanger outlet; check the circulator in the pump group and the loop valves below the boiler.
  4. Test: after the boiler cools, prove the circulator runs and moves water on a call and that no valve is closed. Strong proven flow with repeated trips means the sensor is reading high and must be tested against a thermometer.
  5. End at the pinpoint: fix the flow fault or replace the supply Temperature sensor as the tests condemn, let the boiler cool, then reset. Technician work. → Shop the temperature sensor at Amazon

Did that fix it?

Worked through the steps? Say where you landed - it pinpoints what to do next.

Parts that commonly fix the 4A 218 code

Parts run $25–$80

Typical ranges, checked Nov 2026. Your model’s exact part can land outside them.

What fixed yours?

Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.

Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.

Manual & model number

Working on a specific model? The official Bosch manual is on Bosch's support site — you'll need your model number.

Find your model number on the rating plate on the boiler jacket, often behind the front panel. It's the key to the right manual pages and the right parts.

Related Bosch Boiler Buderus Logamax plus GB162 error codes

See all Bosch Buderus Logamax plus GB162 codes & guides →