Lochinvar Boiler Knight 81-286 (SMART SYSTEM) Flue Sensor Fault
What this problem usually means
Flue Sensor Fault is a manual reset lockout raised when the control reads the flue sensor as open or shorted. The flue sensor watches stack temperature, so the boiler locks out without a valid reading. Wiring, then sensor resistance against Table 3-2D, then the control module is the test order.
Likely causes
- Control reads the flue sensor as open or shorted
- Flue sensor wiring disconnected or damaged
- Faulty flue sensor
- Faulty control module
How to fix it — step by step
- Record the fault before resetting: write down 'Flue Sensor Fault' exactly as shown on the SMART SYSTEM display, and note that most Knight lockouts need a manual reset with the RESET button on the SMART SYSTEM display after the condition is corrected.
- Safety: shut the boiler down, isolate power and close the gas shut-off valve before opening the cabinet or testing wiring. Gas pressure, gas valve and combustion checks are qualified technician work.
- Locate the parts: the flue sensor is fitted in the flue or stack connection at the boiler and wired to the control module, and the fault is read on the SMART SYSTEM display.
- Test: check the wiring to the sensor and make sure it is connected and not damaged, repairing it as needed. Measure the resistance of the sensor and compare it with Table 3-2D on page 35 of the service manual; a reading outside the table condemns the sensor.
- End at the fix: replace the flue sensor if it tests faulty, then press RESET on the SMART SYSTEM display. A proven sensor and wiring pinpoint the control module. → Shop the control module at Amazon
Did that fix it?
Worked through the steps? Say where you landed - it pinpoints what to do next.
Good - you're done. If it comes back, the causes at the top of this page are where to look first.
This fault usually needs a technician - but this is the part they would test first.
Then the likely broken part is the Flue sensor.
Shop the Flue sensor at Amazon
Also tied to this fault: Control module - Shop at Amazon
Parts that commonly fix it
- Flue sensorShop at Amazon
- Control moduleShop at Amazon
What fixed yours?
Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.
Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.
Manual & model number
Find your model number on the rating plate on the boiler jacket, often behind the front panel. It's the key to the right manual pages and the right parts.
Related Lochinvar Boiler Knight 81-286 (SMART SYSTEM) problems
- Flue Temp Diff
- Flue Temp High
- Flue Temp Limit
- Gas Pressure SW
- GV/Relay Fail
- Inlet Sensor Fault
- Louver Proving Sw
- Memory Error
- Outlet ARHL
- Outlet MRHL
- Outlet Sensor Fault
- Outlet Temp Diff
See all Lochinvar Knight 81-286 (SMART SYSTEM) codes & guides →