Lochinvar Boiler Knight 81-286 (SMART SYSTEM) Flue Temp Diff
What this problem usually means
Flue Temp Diff is a manual reset lockout raised when the control module reads an excessive temperature difference between the two sensors in the flue temperature circuit. As with the outlet version, one sensor reading wrong is the usual cause, and both are proved by resistance against Table 3-2D before parameters or the module are blamed.
Likely causes
- Excessive temperature difference between the two sensors
- Faulty flue sensor or sensor wiring
- Control parameter fault
- Faulty control module
How to fix it — step by step
- Record the fault before resetting: write down 'Flue Temp Diff' exactly as shown on the SMART SYSTEM display, and note that most Knight lockouts need a manual reset with the RESET button on the SMART SYSTEM display after the condition is corrected.
- Safety: shut the boiler down, isolate power and close the gas shut-off valve before opening the cabinet or testing wiring. Gas pressure, gas valve and combustion checks are qualified technician work.
- Locate the parts: the flue sensors are fitted in the flue path at the boiler and wired to the control module, and the fault is read on the SMART SYSTEM display.
- Test: check the wiring to the sensors for connection and damage, then measure each sensor's resistance against Table 3-2D on page 35 of the service manual. A sensor far out of line with its pair at the same temperature is the pinpoint.
- End at the fix: replace the condemned sensor, or restore the control parameter defaults from the optional PC software, then press RESET on the SMART SYSTEM display. Sensors and parameters both proven leave the control module. → Shop the control module at Amazon
Did that fix it?
Worked through the steps? Say where you landed - it pinpoints what to do next.
Good - you're done. If it comes back, the causes at the top of this page are where to look first.
This fault usually needs a technician - but this is the part they would test first.
Then the likely broken part is the Flue sensor.
Shop the Flue sensor at Amazon
Also tied to this fault: Control module - Shop at Amazon
Parts that commonly fix it
- Flue sensorShop at Amazon
- Control moduleShop at Amazon
What fixed yours?
Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.
Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.
Manual & model number
Find your model number on the rating plate on the boiler jacket, often behind the front panel. It's the key to the right manual pages and the right parts.
Related Lochinvar Boiler Knight 81-286 (SMART SYSTEM) problems
- Flue Temp High
- Flue Temp Limit
- Gas Pressure SW
- GV/Relay Fail
- Inlet Sensor Fault
- Louver Proving Sw
- Memory Error
- Outlet ARHL
- Outlet MRHL
- Outlet Sensor Fault
- Outlet Temp Diff
- Outlet Temp High
See all Lochinvar Knight 81-286 (SMART SYSTEM) codes & guides →