Lochinvar Boiler Knight 81-286 (SMART SYSTEM) Flow Switch/LWCO
What this problem usually means
Flow Switch/LWCO is a manual reset lockout raised when either the optional flow switch or the optional low water cutoff is not making. The boiler is not proving water flow or a safe water level, so it will not fire. A blown fuse F3 on the control board can also sit behind this fault.
Likely causes
- Flow switch not making
- Low water cutoff not making, low system water
- Closed valves or obstructions in the boiler piping
- Air not purged from the system
- Blown fuse F3 on the control board
How to fix it — step by step
- Record the fault before resetting: write down 'Flow Switch/LWCO' exactly as shown on the SMART SYSTEM display, and note that most Knight lockouts need a manual reset with the RESET button on the SMART SYSTEM display after the condition is corrected.
- Safety: shut the boiler down, isolate power and close the gas shut-off valve before opening the cabinet or testing wiring. Gas pressure, gas valve and combustion checks are qualified technician work.
- Locate the parts: the flow switch and low water cutoff, where fitted, are in the boiler piping circuit, fuse F3 is on the control board inside the cabinet, and the fault is read on the SMART SYSTEM display.
- Test: check boiler pump operation on a call for heat, check for closed valves or obstructions in the boiler piping, and verify the system is full of water with all air purged. If neither device is installed, check for loose or misplaced jumpers instead, and check fuse F3 on the control board.
- End at the fix: restore flow and water level, purge the air, replace fuse F3 if it is blown, then press RESET on the SMART SYSTEM display. A device that still will not make with flow proven is replaced.
Did that fix it?
Worked through the steps? Say where you landed - it pinpoints what to do next.
Good - you're done. If it comes back, the causes at the top of this page are where to look first.
This fault usually needs a technician - but this is the part they would test first.
Then the likely broken part is the Flow switch.
Shop the Flow switch at Amazon
Also tied to this fault: Low water cutoff - Shop at Amazon; Fuse F3 - Shop at Amazon
Parts that commonly fix it
- Flow switchShop at Amazon
- Low water cutoffShop at Amazon
- Fuse F3Shop at Amazon
What fixed yours?
Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.
Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.
Manual & model number
Find your model number on the rating plate on the boiler jacket, often behind the front panel. It's the key to the right manual pages and the right parts.
Related Lochinvar Boiler Knight 81-286 (SMART SYSTEM) problems
- Flue Sensor Fault
- Flue Temp Diff
- Flue Temp High
- Flue Temp Limit
- Gas Pressure SW
- GV/Relay Fail
- Inlet Sensor Fault
- Louver Proving Sw
- Memory Error
- Outlet ARHL
- Outlet MRHL
- Outlet Sensor Fault
See all Lochinvar Knight 81-286 (SMART SYSTEM) codes & guides →