Lochinvar Boiler Knight 81-286 (SMART SYSTEM) Flame Fail Ign

What this problem usually means

Flame Fail Ign is a manual reset lockout raised when the unit has failed to prove main burner ignition after four attempts. The full check sequence runs from the spark electrode and grounding through supply gas pressure, the gas valve's 24 vac supply and gas flow, the flame sensor, the heat exchanger and the burner. Work it in that order and the failing stage is the pinpoint.

Likely causes

  1. Failed to prove main burner ignition after four attempts
  2. Damaged spark electrode or wiring
  3. Poor electrical grounding
  4. Supply gas pressure out of range
  5. Gas valve not opening or no 24 vac to the gas valve
  6. Faulty flame sensor
  7. Dirty heat exchanger or burner

How to fix it — step by step

  1. Record the fault before resetting: write down 'Flame Fail Ign' exactly as shown on the SMART SYSTEM display, and note that most Knight lockouts need a manual reset with the RESET button on the SMART SYSTEM display after the condition is corrected.
  2. Safety: shut the boiler down, isolate power and close the gas shut-off valve before opening the cabinet or testing wiring. Gas pressure, gas valve and combustion checks are qualified technician work.
  3. Locate the parts: the spark electrode and flame sensor are in the burner assembly, the gas valve is in the gas train inside the cabinet with a 2-pin 24 vac connection at the side of the main control board, and the fault is read on the SMART SYSTEM display.
  4. Test: inspect the spark electrode and wiring and check grounding, then measure incoming supply gas pressure against 4 to 14 inches w.c. for natural gas or 8 to 14 for LP, and confirm the plastic hose from the gas valve to the air inlet is connected and undamaged and the vent and air intake pipes are clear. Then check for 24 vac to the gas valve during ignition: no voltage condemns the main control board, voltage present means check the wiring, and with a manometer on the valve outlet tap a missing pressure change when the valve is energised condemns the gas valve.
  5. End at the fix: replace the part the sequence condemns, electrode, gas valve, flame sensor, burner or main control board, clean the heat exchanger if it is fouled, then press RESET on the SMART SYSTEM display. Gas valve and control board replacement are technician work. → Shop the main control board at Amazon → Shop the flame sensor at Amazon

Did that fix it?

Worked through the steps? Say where you landed - it pinpoints what to do next.

Parts that commonly fix it

Parts run $10–$355

Typical ranges, checked Nov 2026. Your model’s exact part can land outside them.

What fixed yours?

Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.

Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.