Lochinvar Boiler Knight 81-286 (SMART SYSTEM) Flame Sequence

What this problem usually means

Flame Sequence is a manual reset lockout raised when the flame detector circuit is seeing a flame signal while no flame is present. A false flame signal blocks start up for safety. The checks are electrical first: supply voltage polarity, external wiring feeding voltage back, a clean flame rod, and the internal wiring connections.

Likely causes

  1. Flame signal present with no flame
  2. Incorrect supply voltage polarity
  3. Voltage feedback from external wiring
  4. Dirty flame rod
  5. Bad internal wiring connections

How to fix it — step by step

  1. Record the fault before resetting: write down 'Flame Sequence' exactly as shown on the SMART SYSTEM display, and note that most Knight lockouts need a manual reset with the RESET button on the SMART SYSTEM display after the condition is corrected.
  2. Safety: shut the boiler down, isolate power and close the gas shut-off valve before opening the cabinet or testing wiring. Gas pressure, gas valve and combustion checks are qualified technician work.
  3. Locate the parts: the flame rod is in the burner assembly, its circuit runs through the internal wiring to the main control board, and the fault is read on the SMART SYSTEM display.
  4. Test: check the supply voltage for proper polarity and check external wiring for voltage feedback into the flame circuit. Then check the flame rod is clean and the internal wiring connections are sound; each clean result moves the suspicion one step closer to the main control board.
  5. End at the fix: correct the polarity, feedback or wiring fault found, or clean the flame rod, then press RESET on the SMART SYSTEM display. If every external check passes, the pinpoint is the main control board and it is replaced.

Did that fix it?

Worked through the steps? Say where you landed - it pinpoints what to do next.

Parts that commonly fix it

Parts run $10–$60

Typical ranges, checked Nov 2026. Your model’s exact part can land outside them.

What fixed yours?

Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.

Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.