Lochinvar Boiler Knight 81-286 (SMART SYSTEM) Flue Temp Limit

What this problem usually means

Flue Temp Limit is a manual reset lockout raised when the stack temperature has exceeded the Flue Temp Limit set parameters. High stack temperature usually means heat is not transferring into the water, so the flue side of the heat exchanger is inspected and cleaned, the flue sensor is proved, and the vent and air intake installation is verified.

Likely causes

  1. Stack temperature exceeded the Flue Temp Limit set parameters
  2. Fouled flue side of the heat exchanger
  3. Faulty flue sensor
  4. Obstructed or badly installed vent or air intake pipes

How to fix it — step by step

  1. Record the fault before resetting: write down 'Flue Temp Limit' exactly as shown on the SMART SYSTEM display, and note that most Knight lockouts need a manual reset with the RESET button on the SMART SYSTEM display after the condition is corrected.
  2. Safety: shut the boiler down, isolate power and close the gas shut-off valve before opening the cabinet or testing wiring. Gas pressure, gas valve and combustion checks are qualified technician work.
  3. Locate the parts: the flue side of the heat exchanger is inside the boiler, the flue sensor is in the stack connection, the vent and air intake pipes leave the top of the unit, and the fault is read on the SMART SYSTEM display.
  4. Test: inspect the heat exchanger flue side and clean it if fouled, then inspect the flue sensor and its wiring and measure its resistance against Table 3-2D on page 35 of the service manual. Verify the vent and air intake pipes are properly installed with no obstructions; a clean exchanger, clear venting and a good sensor leave the main control board. → Shop the flue sensor at Amazon
  5. End at the fix: clean the heat exchanger or replace the flue sensor as the tests condemn, clear the venting, then press RESET on the SMART SYSTEM display. All external causes proven good pinpoints the main control board.

Did that fix it?

Worked through the steps? Say where you landed - it pinpoints what to do next.

Parts that commonly fix it

What fixed yours?

Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.

Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.

Manual & model number

Find your model number on the rating plate on the boiler jacket, often behind the front panel. It's the key to the right manual pages and the right parts.