Lochinvar Boiler Knight 81-286 (SMART SYSTEM) Gas Pressure SW

What this problem usually means

Gas Pressure SW is a manual reset lockout. Either the optional manual reset low gas pressure switch or the optional manual reset high gas pressure switch has tripped, or the gas pressure switch contacts on the Low Voltage Connection Board are open. Supply gas pressure outside its range is the root cause to prove first: natural gas should be between 4 and 14 inches w.c. and LP gas between 8 and 14 inches w.c.

Likely causes

  1. Low or high gas pressure switch tripped
  2. Supply gas pressure out of range, natural gas 4-14 in. w.c., LP 8-14 in. w.c.
  3. Open gas pressure switch contacts on the Low Voltage Connection Board
  4. Loose or misplaced jumper where no pressure switch is installed

How to fix it — step by step

  1. Record the fault before resetting: write down 'Gas Pressure SW' exactly as shown on the SMART SYSTEM display, and note that most Knight lockouts need a manual reset with the RESET button on the SMART SYSTEM display after the condition is corrected.
  2. Safety: shut the boiler down, isolate power and close the gas shut-off valve before opening the cabinet or testing wiring. Gas pressure, gas valve and combustion checks are qualified technician work.
  3. Locate the parts: the gas pressure switches, where fitted, are in the gas supply line at the boiler, their contacts land on the Low Voltage Connection Board inside the control compartment, and the fault is read on the SMART SYSTEM display.
  4. Test: reset the pressure switches, then measure the supply gas pressure and compare it with the 4 to 14 inches w.c. range for natural gas or 8 to 14 for LP. Pressure in range with the lockout returning means check for a loose or misplaced jumper if switches are not installed, and for any device wired across the switch terminals on the Low Voltage Connection Board.
  5. End at the fix: correct the supply gas pressure if it is out of range, refit the jumper or wiring fault found, then press RESET on the SMART SYSTEM display. A switch that trips again on proven pressure is itself faulty and is replaced.

Did that fix it?

Worked through the steps? Say where you landed - it pinpoints what to do next.

Parts that commonly fix it

Parts run $50–$205

Typical ranges, checked Nov 2026. Your model’s exact part can land outside them.

What fixed yours?

Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.

Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.